High-performance TeSys F nonreversing contactor for 600V, 330A applications with 120VAC, 40-65Hz coil.
Product ModelLC1F330G722L
Product ID33412
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh operating cycles per hour for reliable performance.
2
FeatureDesigned for 600V, 330A applications with 120VAC, 40-65Hz coil.
3
FeatureFast closing and opening times for efficient control.
4
FeatureFlexible control circuit terminals for easy installation.
5
FeatureMeets stringent EMC requirements for a reliable operation.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive loadMotor control
Utilisation category
AC-3AC-1AC-4
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Uc] control circuit voltage
120 V AC 40...400 Hz
[Ie] rated operational current
400 A (at <104 °F (40 °C)) at <= 440 V AC AC-1330 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
400 A (at 104 °F (40 °C))
Rated breaking capacity
2640 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
2650 A 104 °F (40 °C) - 10 s1800 A 104 °F (40 °C) - 30 s1300 A 104 °F (40 °C) - 1 min900 A 104 °F (40 °C) - 3 min750 A 104 °F (40 °C) - 10 min
Associated fuse rating
400 A aM at <= 440 V500 A gG at <= 440 V
Average impedance
0.28 mOhm - Ith 400 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
44 W AC-131 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
160 kW at 380...400 V AC 50/60 Hz (AC-3)180 kW at 415 V AC 50/60 Hz (AC-3)200 kW at 440 V AC 50/60 Hz (AC-3)200 kW at 500 V AC 50/60 Hz (AC-3)220 kW at 660...690 V AC 50/60 Hz (AC-3)160 kW at 1000 V AC 50/60 Hz (AC-3)100 kW at 220...230 V AC 50/60 Hz (AC-3)59 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
75 hp at 200 V AC100 hp at 230 V AC200 hp at 460 V AC250 hp at 575 V AC
EN 60947-4-1IEC 60947-4-1IEC 60947-1EN 60947-1JIS C8201-4-1
Product Certifications
RMRoSULRINABVCBDNVABSLROS (Lloyds register of shipping)CSA
Hold-in power consumption in VA
10 VA 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))
IP degree of protection
IP20 front face with shrouds IEC 60529IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23...131 °F (-5...55 °C)
Ambient Air Temperature for Storage
-76...176 °F (-60...80 °C)
Permissible ambient air temperature around the device
-40...158 °F (-40...70 °C)
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 HzShocks contactor closed15 Gn for 11 msVibrations contactor closed5 Gn, 5...300 HzShocks contactor open6 Gn for 11 ms
Height
14.8 in (375 mm)
Width
8.4 in (213 mm)
Depth
8.6 in (219 mm)
Operating altitude
9842.52 ft (3000 m) without derating
LC1F330G722L - TeSys F Nonreversing Contactor | INDPRT