Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protectionInternal supply 24 V DC 21...27 V), <200 A overload and short-circuit protection
Sampling duration
2 ms +/- 0.5 ms F discrete2 ms +/- 0.5 ms R discrete2 ms +/- 0.5 ms RES discrete3.5 ms +/- 0.5 ms VIA analog22 ms +/- 0.5 ms VIB analog
Response time
FM 2 ms +/- 0.5 ms analogFLA, FLC 7 ms +/- 0.5 ms discreteFLB, FLC 7 ms +/- 0.5 ms discreteRY, RC 7 ms +/- 0.5 ms discrete
Accuracy
+/- 0.6 % VIA) for a temperature variation 60 °C+/- 0.6 % VIB) for a temperature variation 60 °C+/- 1 % FM) for a temperature variation 60 °C
Linearity error
VIA +/- 0.15 % of maximum value inputVIB +/- 0.15 % of maximum value inputFM +/- 0.2 % output
Analogue output type
FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bitsFM switch-configurable current 0...20 mA 970 Ohm 10 bits
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R)2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R)2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R)
Discrete input type
F programmable 24 V DC level 1 PLC 4700 OhmR programmable 24 V DC level 1 PLC 4700 OhmRES programmable 24 V DC level 1 PLC 4700 Ohm
3535 V DC between earth and power terminals5092 V DC between control and power terminals
Insulation resistance
>= 1 mOhm 500 V DC for 1 minute
Frequency resolution
Display unit 0.1 HzAnalog input 0.024/50 Hz
Communication Service
Write multiple registers (16) 2 words maximumRead device identification (43)Write single register (06)Time out setting from 0.1 to 100 sRead holding registers (03) 2 words maximumMonitoring inhibitable
Option card
Communication card LonWorks
Functionality
Mid
Specific application
HVAC
Discrete output number
2
Analogue input number
2
Analogue input type
VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bitsVIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bitsVIB configurable PTC probe 0...6 probes 1500 OhmVIA switch-configurable current 0...20 mA 250 Ohm 10 bits
Analogue output number
1
Physical interface
2-wire RS 485
Connector Type
1 open style1 RJ45
Transmission Rate
9600 bps or 19200 bps
Transmission frame
RTU
Number of addresses
1...247
Data format
8 bits, 1 stop, odd even or no configurable parity
Type of polarization
No impedance
Asynchronous motor control profile
Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)Flux vector control without sensor, standardVoltage/frequency ratio, 5 pointsVoltage/frequency ratio, 2 pointsVoltage/frequency ratio - Energy Saving, quadratic U/f
Torque accuracy
+/- 15 %
Transient overtorque
120 % of nominal motor torque +/- 10 % 60 s
Acceleration and deceleration ramps
Linear adjustable separately from 0.01 to 3200 sAutomatic based on the load
Motor slip compensation
Automatic whatever the loadAdjustableNot available in voltage/frequency ratio motor control
Switching frequency
6...16 kHz adjustable12...16 kHz with derating factor
Nominal switching frequency
12 kHz
Braking to standstill
By DC injection
Network Frequency
47.5...63 Hz
Prospective line Isc
22 kA
Protection type
Overheating protection driveThermal power stage driveShort-circuit between motor phases driveInput phase breaks driveOvercurrent between output phases and earth driveOvervoltages on the DC bus driveBreak on the control circuit driveAgainst exceeding limit speed driveLine supply overvoltage and undervoltage driveLine supply undervoltage driveAgainst input phase loss driveThermal protection motorMotor phase break motorWith PTC probes motor
Width
9.06 in (230 mm)
Height
13.4 in (340 mm)
Depth
8.2 in (208 mm)
Net Weight
24.14 lb(US) (10.95 kg)
Pollution degree
3 IEC 61800-5-1
Vibration resistance
1.5 mm 3...13 Hz)IEC 60068-2-61 gn 13...200 Hz)EN/IEC 60068-2-8
3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m<= 3280.84 ft (1000 m) without derating
Relative humidity
5...95 % without condensation IEC 60068-2-35...95 % without dripping water IEC 60068-2-3
Ambient air temperature for operation