High-durability and reliable TeSys F contactor for motor applications up to 250kW@400V.
Product ModelLC1F500F722L
Product ID33282
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-durability design for extended operating cycles
2
FeatureReliable performance in harsh industrial environments
3
FeatureSuitable for motor applications up to 250kW@400V
4
FeatureLow sealed consumption 110V AC coil
5
FeatureIdeal for use in industrial settings requiring high reliability
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive loadMotor control
Utilisation category
AC-1AC-4AC-3
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Uc] control circuit voltage
110 V AC 40...400 Hz
[Ie] rated operational current
700 A (at <104 °F (40 °C)) at <= 440 V AC AC-1500 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
700 A (at 104 °F (40 °C))
Rated breaking capacity
4000 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
4200 A 104 °F (40 °C) - 10 s3200 A 104 °F (40 °C) - 30 s2400 A 104 °F (40 °C) - 1 min1500 A 104 °F (40 °C) - 3 min1200 A 104 °F (40 °C) - 10 min
Associated fuse rating
500 A aM at <= 440 V800 A gG at <= 440 V
Average impedance
0.18 mOhm - Ith 700 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
250 kW at 380...400 V AC 50/60 Hz (AC-3)280 kW at 415 V AC 50/60 Hz (AC-3)295 kW at 440 V AC 50/60 Hz (AC-3)355 kW at 500 V AC 50/60 Hz (AC-3)335 kW at 660...690 V AC 50/60 Hz (AC-3)335 kW at 1000 V AC 50/60 Hz (AC-3)147 kW at 220...230 V AC 50/60 Hz (AC-3)80 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
150 hp at 200 V AC200 hp at 230 V AC400 hp at 460 V AC500 hp at 575 V AC