The LC1F2600 TeSys F 3P(3NO) AC-1 contactor by Schneider Electric offers reliable and efficient electrical control for a wide range of applications.
Product ModelLC1F2600
Product ID33232
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh reliability and efficiency in electrical control
2
FeatureWide operating temperature range from -40°F to 140°F (-40°C to 60°C)
3
FeatureDesigned for 3P(3NO) AC-1 applications
4
FeatureVibration resistance up to 300 Hz
5
FeatureSuitable for various industrial and commercial use cases
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Product name
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz
[Ie] rated operational current
2600 A 140 °F (60 °C)) <= 440 V AC AC-1
[Uc] control circuit voltage
110...500 V AC 40...400 Hz with LX1/LX9 coil110...440 V DC with LX4 coil
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
2600 A (at 140 °F (60 °C))
Irms rated making capacity
3900 A AC conforming to IEC 60947-4-1
Rated breaking capacity
3900 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
12000 A 104 °F (40 °C) - 10 s9000 A 104 °F (40 °C) - 30 s7000 A 104 °F (40 °C) - 1 min6000 A 104 °F (40 °C) - 3 min4000 A 104 °F (40 °C) - 10 min
Associated fuse rating
2500 A gG at <= 440 V
Average impedance
0.1 mOhm - Ith 2600 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1
Power dissipation per pole
250 W AC-1
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coilDrop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coilOperational: 0.85...1.1 Uc DC with LX4 coilDrop-out: 0.2...0.35 Uc DC with LX4 coil
Heat dissipation
25 W
Operating time
40...80 ms closing with LX1/LX9 coil100...200 ms opening with LX1/LX9 coil60...70 ms closing with LX4 coil40...50 ms opening with LX4 coil
2200...2700 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil2130...2880 VA (at 68 °F (20 °C))with LX4 coil
Hold-in power consumption in VA
37.4...50.6 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil13...25 VA (at 68 °F (20 °C))with LX4 coil
Maximum operating rate
600 cyc/h 131 °F (55 °C)
compatibility code
LC1F
IP degree of protection
IP20 front face with shrouds IEC 60529IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23...104 °F (-5...40 °C)
Ambient Air Temperature for Storage
-76...176 °F (-60...80 °C)
Permissible ambient air temperature around the device
-40...140 °F (-40...60 °C)
Operating altitude
9842.52 ft (3000 m) without derating
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 HzVibrations contactor closed4 Gn, 5...300 HzShocks contactor open6 Gn for 1/2 sine wave (11 ms)Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Height
15.04 in (382 mm)
Width
20.4 in (519 mm)
Depth
9.9 in (251 mm)
Net Weight
79.4 lb(US) (36 kg)
LC1F2600 TeSys F 3P(3NO) AC-1 Contactor by Schneider Electric | INDPRT