The LC1F1857F7 TeSys F contactor is a high-performance solution for industrial applications, offering reliable operation and efficient control.
Product ModelLC1F1857F7
Product ID
33183
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-performance operation with 2400 cycles per hour.
2
FeatureReliable operation in temperatures up to 131°F (55°C).
3
FeatureFast closing and opening times for efficient control.
4
FeatureFlexible control circuit screw clamp terminals for easy installation.
5
FeatureDesigned for 3P (3 NO) AC3, 440V, and 275A coil with 110V AC control circuit.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Induction furnace
Utilisation category
AC-3AC-1AC-4
Poles description
3P
[Ue] rated operational voltage
<= 460 V DC<= 690 V AC 50/60 Hz
[Uc] control circuit voltage
110 V AC 40...400 Hz
[Ie] rated operational current
275 A (at <104 °F (40 °C)) at <= 440 V AC-1185 A (at <131 °F (55 °C)) at <= 440 V AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
275 A (at 104 °F (40 °C))
Rated breaking capacity
1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1500 A 104 °F (40 °C) - 10 s920 A 104 °F (40 °C) - 30 s740 A 104 °F (40 °C) - 1 min500 A 104 °F (40 °C) - 3 min400 A 104 °F (40 °C) - 10 min
Associated fuse rating
200 A aM at <= 440 V315 A gG at <= 440 V
Average impedance
0.33 mOhm - Ith 275 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
12 W AC-325 W AC-1
Overvoltage category
III
power pole contact composition
1 NO (early break) + 2 NO
Motor power kW
90 kW at 380...400 V AC 50/60 Hz (AC-3)100 kW at 415 V AC 50/60 Hz (AC-3)100 kW at 440 V AC 50/60 Hz (AC-3)110 kW at 500 V AC 50/60 Hz (AC-3)110 kW at 660...690 V AC 50/60 Hz (AC-3)55 kW at 220...230 V AC 50/60 Hz (AC-3)33 kW at 400 V AC 50/60 Hz (AC-4)