TeSys F nonreversing contactor for reliable motor control applications.
Product ModelLC1F115G622L
Product ID33164
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh reliability and durability for long-lasting performance.
2
FeatureDesigned for motor control applications up to 55kW at 400V.
3
Feature120V 60Hz AC coil for efficient operation.
4
Feature2 bars 20 x 3 mm power circuit for secure connections.
5
Feature23...35 ms closing and 5...15 ms opening times for precise control.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor controlResistive load
Utilisation category
AC-1AC-4AC-3
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Uc] control circuit voltage
120 V AC 60 Hz
[Ie] rated operational current
200 A (at <104 °F (40 °C)) at <= 440 V AC AC-1115 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
200 A (at 104 °F (40 °C))
Rated breaking capacity
920 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1100 A 104 °F (40 °C) - 10 s640 A 104 °F (40 °C) - 30 s520 A 104 °F (40 °C) - 1 min400 A 104 °F (40 °C) - 3 min320 A 104 °F (40 °C) - 10 min
Associated fuse rating
125 A aM at <= 440 V200 A gG at <= 440 V
Average impedance
0.37 mOhm - Ith 200 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
15 W AC-15 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
55 kW at 380...400 V AC 50/60 Hz (AC-3)59 kW at 415 V AC 50/60 Hz (AC-3)59 kW at 440 V AC 50/60 Hz (AC-3)75 kW at 500 V AC 50/60 Hz (AC-3)80 kW at 660...690 V AC 50/60 Hz (AC-3)65 kW at 1000 V AC 50/60 Hz (AC-3)30 kW at 220...230 V AC 50/60 Hz (AC-3)18.5 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
30 hp at 200 V AC40 hp at 230 V AC75 hp at 460 V AC100 hp at 575 V AC
BVRINACBDNVABSLROS (Lloyds register of shipping)ULCCCRMRoS
Hold-in power consumption in VA
55 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
IP degree of protection
IP2X front face with shrouds IEC 60529IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
-40...140 °F (-40...60 °C)
Ambient Air Temperature for Storage
-76...176 °F (-60...80 °C)
Permissible ambient air temperature around the device
140...158 °F (60...70 °C) at Uc
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 HzVibrations contactor closed6 Gn, 5...300 HzShocks contactor open9 Gn for 11 msShocks contactor closed15 Gn for 11 ms