The LC1F150Q7 TeSys F Contactor is a 3-pole, 3-NO motor control device with an AC-3 rating, suitable for applications up to 440V and 150A.
Product ModelLC1F150Q7
Product ID33120
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh reliability and durability for long-lasting performance.
2
FeatureEasy installation with screw clamp terminals for quick setup.
3
FeatureDesigned for motor control applications, ensuring efficient operation.
4
FeatureCompact design suitable for DIN rail mounting or panel installation.
5
FeatureCompliant with TeSys F range specifications for consistent quality.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor controlResistive load
Utilisation category
AC-1AC-4AC-3
Poles description
3P
[Ue] rated operational voltage
<= 690 V AC 50/60 Hz<= 460 V DC
[Uc] control circuit voltage
380 V AC 40...400 Hz
[Ie] rated operational current
250 A (at <104 °F (40 °C)) at <= 440 V AC-1150 A (at <131 °F (55 °C)) at <= 440 V AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
250 A (at 104 °F (40 °C))
Rated breaking capacity
1200 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1200 A 104 °F (40 °C) - 10 s700 A 104 °F (40 °C) - 30 s600 A 104 °F (40 °C) - 1 min450 A 104 °F (40 °C) - 3 min350 A 104 °F (40 °C) - 10 min
Associated fuse rating
160 A aM at <= 440 V250 A gG at <= 440 V
Average impedance
0.35 mOhm - Ith 250 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
22 W AC-18 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
75 kW at 380...400 V AC 50/60 Hz (AC-3)80 kW at 415 V AC 50/60 Hz (AC-3)80 kW at 440 V AC 50/60 Hz (AC-3)90 kW at 500 V AC 50/60 Hz (AC-3)100 kW at 660...690 V AC 50/60 Hz (AC-3)40 kW at 220...230 V AC 50/60 Hz (AC-3)22 kW at 400 V AC 50/60 Hz (AC-4)