The LC1F150E5 TeSys F contactor is a high-performance electrical component designed for reliable operation in various applications.
Product ModelLC1F150E5
Product ID33096
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-performance electrical component for reliable operation.
2
FeatureHandles up to 250 A at 440 V AC-3, ensuring efficient power distribution.
3
FeatureCompliant with IEC 60947-4-1 and VDE 0110 group C standards.
4
FeatureIdeal for applications requiring high current ratings and efficient AC-3 performance.
5
FeatureDesigned with safety and reliability in mind, suitable for a wide range of electrical installations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor controlResistive load
Utilisation category
AC-3AC-4AC-1
Poles description
3P
[Ue] rated operational voltage
<= 690 V AC 50/60 Hz<= 460 V DC
[Uc] control circuit voltage
48 V AC 50 Hz
[Ie] rated operational current
250 A (at <104 °F (40 °C)) at <= 440 V AC-1150 A (at <131 °F (55 °C)) at <= 440 V AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
250 A (at 104 °F (40 °C))
Rated breaking capacity
1200 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1200 A 104 °F (40 °C) - 10 s700 A 104 °F (40 °C) - 30 s600 A 104 °F (40 °C) - 1 min450 A 104 °F (40 °C) - 3 min350 A 104 °F (40 °C) - 10 min
Associated fuse rating
160 A aM at <= 440 V250 A gG at <= 440 V
Average impedance
0.35 mOhm - Ith 250 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
22 W AC-18 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
75 kW at 380...400 V AC 50/60 Hz (AC-3)80 kW at 415 V AC 50/60 Hz (AC-3)80 kW at 440 V AC 50/60 Hz (AC-3)90 kW at 500 V AC 50/60 Hz (AC-3)100 kW at 660...690 V AC 50/60 Hz (AC-3)40 kW at 220...230 V AC 50/60 Hz (AC-3)22 kW at 400 V AC 50/60 Hz (AC-4)