The LC1F150BD22L TeSys F nonreversing contactor is a high-performance motor control solution from Schneider Electric, ensuring reliable operation and efficient power management.
Product ModelLC1F150BD22L
Product ID33095
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-performance motor control for efficient power management.
2
FeatureReliable operation in a wide range of applications.
3
FeatureCompliant with international standards (IEC 60947-1, IEC 60947-4-1).
4
FeatureDesigned for durability and long service life.
5
FeatureEasy integration with various control systems.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor controlResistive load
Utilisation category
AC-4AC-3AC-1
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Uc] control circuit voltage
24 V DC
[Ie] rated operational current
250 A (at <104 °F (40 °C)) at <= 440 V AC AC-1150 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
250 A (at 104 °F (40 °C))
Rated breaking capacity
1200 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1200 A 104 °F (40 °C) - 10 s700 A 104 °F (40 °C) - 30 s600 A 104 °F (40 °C) - 1 min450 A 104 °F (40 °C) - 3 min350 A 104 °F (40 °C) - 10 min
Associated fuse rating
160 A aM at <= 440 V250 A gG at <= 440 V
Average impedance
0.35 mOhm - Ith 250 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
22 W AC-18 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
65 kW at 1000 V AC 50/60 Hz (AC-3)75 kW at 380...400 V AC 50/60 Hz (AC-3)80 kW at 415 V AC 50/60 Hz (AC-3)80 kW at 440 V AC 50/60 Hz (AC-3)90 kW at 500 V AC 50/60 Hz (AC-3)100 kW at 660...690 V AC 50/60 Hz (AC-3)40 kW at 220...230 V AC 50/60 Hz (AC-3)22 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
40 hp at 200 V AC50 hp at 230 V AC100 hp at 460 V AC125 hp at 575 V AC
RMRoSULDNVLROS (Lloyds register of shipping)CCCCBABSRINABV
IP degree of protection
IP2X front face with shrouds IEC 60529IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
-40...140 °F (-40...60 °C)
Ambient Air Temperature for Storage
-76...176 °F (-60...80 °C)
Permissible ambient air temperature around the device
140...158 °F (60...70 °C) at Uc
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 HzVibrations contactor closed6 Gn, 5...300 HzShocks contactor open9 Gn for 11 msShocks contactor closed15 Gn for 11 ms