The LC1F185N522L TeSys F non-reversing contactor by Schneider Electric is designed for high-performance applications, offering reliable and efficient control solutions.
Product ModelLC1F185N522L
Product ID33054
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-performance motor control for demanding applications
2
FeatureReliable and efficient operation with low heat dissipation
3
FeatureWide range of control circuit voltages for flexibility
4
FeatureCompact design with robust mechanical construction
5
FeatureCompliance with international standards for safety and performance
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Motor controlResistive load
Utilisation category
AC-3AC-4AC-1
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Uc] control circuit voltage
415 V AC 50 Hz
[Ie] rated operational current
275 A (at <104 °F (40 °C)) at <= 440 V AC AC-1185 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
275 A (at 104 °F (40 °C))
Rated breaking capacity
1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
1500 A 104 °F (40 °C) - 10 s920 A 104 °F (40 °C) - 30 s740 A 104 °F (40 °C) - 1 min500 A 104 °F (40 °C) - 3 min400 A 104 °F (40 °C) - 10 min
Associated fuse rating
200 A aM at <= 440 V315 A gG at <= 440 V
Average impedance
0.33 mOhm - Ith 275 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Power dissipation per pole
12 W AC-325 W AC-1
Overvoltage category
III
power pole contact composition
3 NO
Auxiliary contact composition
2 NO + 2 NC
Motor power kW
90 kW at 380...400 V AC 50/60 Hz (AC-3)100 kW at 415 V AC 50/60 Hz (AC-3)100 kW at 440 V AC 50/60 Hz (AC-3)110 kW at 500 V AC 50/60 Hz (AC-3)110 kW at 660...690 V AC 50/60 Hz (AC-3)100 kW at 1000 V AC 50/60 Hz (AC-3)55 kW at 220...230 V AC 50/60 Hz (AC-3)33 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
50 hp at 200 V AC60 hp at 230 V AC125 hp at 460 V AC150 hp at 575 V AC
JIS C8201-4-1IEC 60947-4-1IEC 60947-1EN 60947-1EN 60947-4-1
Product Certifications
LROS (Lloyds register of shipping)CCCULCBBVDNVRINARMRoSABS
Hold-in power consumption in VA
55 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
IP degree of protection
IP2X front face with shrouds IEC 60529IP2X front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23...131 °F (-5...55 °C)
Ambient Air Temperature for Storage
-76...176 °F (-60...80 °C)
Permissible ambient air temperature around the device
-40...158 °F (-40...70 °C)
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 HzShocks contactor closed15 Gn for 11 msVibrations contactor closed5 Gn, 5...300 HzShocks contactor open7 Gn for 11 ms