Schneider Electric LC1D80004T6 contactor for motor control applications with 4NO contacts and 120 VAC coil voltage.
Product ModelLC1D80004T6
Product ID32702
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-frequency operation compatible up to 400 Hz
2
FeatureRobust construction with open enclosure
3
Feature4NO contact configuration for reliable switching
4
Feature120 VAC coil voltage for efficient operation
5
Feature3600 cycles/hr operating cycles for continuous use
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1AC-3AC-3eAC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 300 V DC 25...400 HzPower circuit <= 690 V AC
[Ie] rated operational current
125 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit80 A (at <140 °F (60 °C)) AC AC-3 for power circuit80 A (at <140 °F (60 °C)) AC AC-3e for power circuit55 A (at <140 °F (60 °C)) AC AC-4 for power circuit
[Uc] control circuit voltage
480 V AC 60 Hz
compatibility code
LC1D
Pole contact composition
4 NO
Protective cover
Without
[Ith] conventional free air thermal current
125 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
640 A 104 °F (40 °C) - 10 s for power circuit990 A 104 °F (40 °C) - 1 s for power circuit135 A 104 °F (40 °C) - 10 min for power circuit320 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating
200 A gG at <= 690 V coordination type 1 for power circuit160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Power dissipation per pole
12.5 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULPower circuit 1000 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10 Mcycles
Electrical durability
0.8 Mcycles 125 A AC-1 <= 440 V
Control circuit type
AC 60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.85...1.1 Uc -40...131 °F (-40...55 °C) operational AC 60 Hz0.3...0.6 Uc -40...158 °F (-40...70 °C) drop-out AC 60 Hz1...1.1 Uc 131...158 °F (55...70 °C) operational AC 60 Hz
Vibrations contactor open 2 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor closed 10 Gn for 11 ms)