The Schneider Electric LC1D80008T6 TeSys D Contactor is a high-performance, non-reversing contactor suitable for a wide range of industrial applications.
Product ModelLC1D80008T6
Product ID32657
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureEfficient motor control with up to 80% less energy consumption
2
FeatureHigh fault short circuit current ratings for flexible component selection
3
FeatureBuilt-in auxiliary contacts for enhanced functionality
4
FeatureCompact dimensions and open enclosure for easy installation
5
FeaturePerfect integration in control systems for simplified maintenance
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 300 V DCPower circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
125 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
480 V AC 60 Hz
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
Without
[Ith] conventional free air thermal current
125 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1100 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
640 A 104 °F (40 °C) - 10 s for power circuit990 A 104 °F (40 °C) - 1 s for power circuit135 A 104 °F (40 °C) - 10 min for power circuit320 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating
200 A gG at <= 690 V coordination type 1 for power circuit160 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.8 mOhm - Ith 125 A 50 Hz for power circuit
Power dissipation per pole
12.5 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULPower circuit 1000 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10 Mcycles
Electrical durability
0.8 Mcycles 125 A AC-1 <= 440 V
Control circuit type
AC 60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.85...1.1 Uc -40...131 °F (-40...55 °C) operational AC 60 Hz0.3...0.6 Uc -40...158 °F (-40...70 °C) drop-out AC 60 Hz1...1.1 Uc 131...158 °F (55...70 °C) operational AC 60 Hz
CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
Product Certifications
DNVLROS (Lloyds register of shipping)GLGOSTRINABVCCCCSAUL
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-40...140 °F (-40...60 °C)140...158 °F (60...70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor closed 10 Gn for 11 ms)