The LC1D65004W6 contactor by Schneider Electric is a high-performance electrical component designed for 690V, 80A, and 4-pole configurations.
Product ModelLC1D65004W6
Product ID32473
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-performance electrical component designed for 690V, 80A, and 4-pole configurations.
2
FeatureReliable and efficient operation in various industrial applications.
3
FeatureIdeal for use in high-voltage systems requiring precise control and safety.
4
FeatureCompliant with international standards for electrical safety and performance.
5
FeatureEnhance your electrical system with our durable and long-lasting contactors.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
TeSys DTeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit 690 V AC 25...400 Hz
[Ie] rated operational current
80 A (at <140 °F (60 °C)) at 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
277 V AC 60 Hz
compatibility code
LC1D
Pole contact composition
4 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for control circuit80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1000 A at 440 V AC for power circuit conforming to IEC 60947140 A AC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity
1000 kA at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for control circuit conforming to IEC 60947-5-1125 A at 690 V coordination type 1 for power circuit125 A at 690 V coordination type 2 for power circuit
Average impedance
1 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
6.3 W AC-39.6 W AC-1
[Ui] rated insulation voltage
Control circuit 600 V CSAControl circuit 600 V ULPower circuit 600 V CSAPower circuit 600 V ULControl circuit 690 V IEC 60947-4-1Power circuit 690 V IEC 60947-4-1
Overvoltage category
III
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6000000 cycles
Control circuit type
AC 60 Hz standard
Coil technology
Without built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.3...0.6 Uc 140 °F (60 °C) drop-out AC 50/60 Hz0.85...1.1 Uc 140 °F (60 °C) operational AC 60 Hz