The LC1D656LE7 contactor by Schneider Electric is a reliable 3P AC3 solution for various industrial applications, offering high current ratings and robust performance.
Product ModelLC1D656LE7
Product ID32315
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureReliable Performance
2
FeatureHigh Current Rating
3
FeatureRobust Design
4
FeatureEasy Installation
5
FeatureCompliance with Standards
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive loadMotor control
Utilisation category
AC-1AC-3AC-3AC-1
Poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
[Ie] rated operational current
80 A (at <140 °F (60 °C)) at 220 V AC AC-1 for power circuit65 A (at <140 °F (60 °C)) at 220 V AC AC-3 for power circuit
[Uc] control circuit voltage
220 V AC 50 Hz
Motor power kW
37 kW at 500 V AC 50 Hz37 kW at 660...690 V AC 50 Hz18.5 kW at 220...230 V AC 50 Hz30 kW at 415 V AC 50 Hz37 kW at 1000 V AC 50 Hz30 kW at 380...400 V AC 50 Hz
Maximum Horse Power Rating
20 hp at 200/208 V AC 60 Hz for 3 phase motors20 hp at 230/240 V AC 60 Hz for 3 phase motors40 hp at 460/480 V AC 60 Hz for 3 phase motors50 hp at 575/600 V AC 60 Hz for 3 phase motors5 hp at 115 V AC 60 Hz for 1 phase motors10 hp at 230/240 V AC 60 Hz for 1 phase motors
compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for control circuit80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1000 A at 440 V for power circuit conforming to IEC 60947140 A AC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity
1000 kA at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
520 A 104 °F (40 °C) - 10 s for power circuit900 A 104 °F (40 °C) - 1 s for power circuit
Associated fuse rating
125 A gG at <= 690 V coordination type 2 for power circuit10 A gG for control circuit conforming to IEC 60947-5-1125 A gG at <= 690 V coordination type 1 for power circuit
Average impedance
1.5 Ohm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
9.6 W AC-16.3 W AC-3
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULControl circuit 690 V IEC 60947-1Power circuit 690 V IEC 60947-1Control circuit 600 V CSAControl circuit 600 V UL
Overvoltage category
III
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Mechanical durability
6000000 cycles
Control circuit type
AC 50 Hz
Coil technology
Without built-in
Control circuit voltage limits
0.85...1.1 Uc -40...140 °F (-40...60 °C) operational AC 60 Hz1...1.1 Uc 140...158 °F (60...70 °C) operational AC 50/60 Hz0.3...0.6 Uc -40...158 °F (-40...70 °C) drop-out AC 50 Hz0.8...1.1 Uc -40...131 °F (-40...55 °C) operational AC 50 Hz
Inrush power in VA
140 VA cos phi 0.75 (at 68 °F (20 °C))160 VA cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
4...5 W at 50/60 Hz for control circuit
Operating time
4...19 ms opening12...26 ms closing
Maximum operating rate
3600 cyc/mn 140 °F (60 °C)
Connections - terminals
Control circuit: lugs - external diameter: 0.3 in (8 mm)Power circuit: lugs - external diameter: 0.6 in (16 mm)