The LC1D65008Z7 TeSys D Contactor is a reliable and efficient power control solution from Schneider Electric, suitable for various industrial applications.
Product ModelLC1D65008Z7
Product ID32310
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureReliable and efficient power control solution
2
FeatureSuitable for various industrial applications
3
FeatureHigh current rating (80 A at 60°C)
4
FeatureCompact design for easy installation
5
FeatureCompliant with IEC 60947 standards
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys D
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 HzPower circuit <= 300 V DC
[Ie] rated operational current
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
21 V AC 50/60 Hz
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
Without
[Ith] conventional free air thermal current
80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
520 A 104 °F (40 °C) - 10 s for power circuit900 A 104 °F (40 °C) - 1 s for power circuit110 A 104 °F (40 °C) - 10 min for power circuit260 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating
125 A gG at <= 690 V coordination type 1 for power circuit125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
9.6 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULPower circuit 690 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6 Mcycles
Electrical durability
1.4 Mcycles 80 A AC-1 <= 440 V
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40...158 °F (-40...70 °C) drop-out AC 50/60 Hz0.8...1.1 Uc -40...140 °F (-40...60 °C) operational AC 50 Hz0.85...1.1 Uc -40...140 °F (-40...60 °C) operational AC 60 Hz1...1.1 Uc 140...158 °F (60...70 °C) operational AC 50/60 Hz
Inrush power in VA
140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))160 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor closed 15 Gn for 11 ms) Shocks contactor open 10 Gn for 11 ms)