The LC1D65008W6 TeSys Deca Contactor is a high-performance, 4-pole contactor ideal for power circuit applications requiring 80 A at 60°C.
Product ModelLC1D65008W6
Product ID32308
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh current rating of 80 A at 60°C for reliable power distribution.
2
FeatureDesigned for AC-1 applications with a voltage range of <= 440V and 277V.
3
Feature4P(2 NO + 2 NC) configuration for versatile control options.
4
FeatureAC 60 Hz coil type for compatibility with standard electrical grids.
5
FeatureSuitable for various industrial and commercial power circuit needs.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys D
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 HzPower circuit <= 300 V DC
[Ie] rated operational current
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
277 V AC 60 Hz
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
Without
[Ith] conventional free air thermal current
80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
520 A 104 °F (40 °C) - 10 s for power circuit900 A 104 °F (40 °C) - 1 s for power circuit110 A 104 °F (40 °C) - 10 min for power circuit260 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating
125 A gG at <= 690 V coordination type 1 for power circuit125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
9.6 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULPower circuit 690 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6 Mcycles
Electrical durability
1.4 Mcycles 80 A AC-1 <= 440 V
Control circuit type
AC 60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.85...1.1 Uc -40...140 °F (-40...60 °C) operational AC 60 Hz0.3...0.6 Uc -40...158 °F (-40...70 °C) drop-out AC 60 Hz1...1.1 Uc 140...158 °F (60...70 °C) operational AC 60 Hz
Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor closed 15 Gn for 11 ms) Shocks contactor open 10 Gn for 11 ms)