The LC1D65008T6 TeSys Deca Contactor is a reliable solution for applications requiring high current ratings and efficient control.
Product ModelLC1D65008T6
Product ID32298
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh current rating up to 80A
2
FeatureEfficient control with screw clamp terminals
3
FeatureFast opening and closing times (4...19 ms and 12...26 ms)
4
FeatureDurable design for 3600 cycles per hour
5
FeatureOperates within a wide temperature range (60 °C)
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys D
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 HzPower circuit <= 300 V DC
[Ie] rated operational current
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
480 V AC 60 Hz
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
Without
[Ith] conventional free air thermal current
80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
520 A 104 °F (40 °C) - 10 s for power circuit900 A 104 °F (40 °C) - 1 s for power circuit110 A 104 °F (40 °C) - 10 min for power circuit260 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating
125 A gG at <= 690 V coordination type 1 for power circuit125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
9.6 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULPower circuit 690 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6 Mcycles
Electrical durability
1.4 Mcycles 80 A AC-1 <= 440 V
Control circuit type
AC 60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.85...1.1 Uc -40...140 °F (-40...60 °C) operational AC 60 Hz0.3...0.6 Uc -40...158 °F (-40...70 °C) drop-out AC 60 Hz1...1.1 Uc 140...158 °F (60...70 °C) operational AC 60 Hz
Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor closed 15 Gn for 11 ms) Shocks contactor open 10 Gn for 11 ms)