The LC1D65008J5 TeSys Deca Contactor is a high-performance electrical component designed for efficient motor control.
Product ModelLC1D65008J5
Product ID32289
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureEfficient motor control with high current capacity
2
FeatureReliable and durable design for long-lasting performance
3
FeatureEasy installation with screw clamp terminals
4
FeatureCompact size for space-saving applications
5
FeatureSuitable for a wide range of industrial applications
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys D
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 HzPower circuit <= 300 V DC
[Ie] rated operational current
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
12 V AC 50 Hz
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
Without
[Ith] conventional free air thermal current
80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
520 A 104 °F (40 °C) - 10 s for power circuit900 A 104 °F (40 °C) - 1 s for power circuit110 A 104 °F (40 °C) - 10 min for power circuit260 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating
125 A gG at <= 690 V coordination type 1 for power circuit125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
9.6 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULPower circuit 690 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6 Mcycles
Electrical durability
1.4 Mcycles 80 A AC-1 <= 440 V
Control circuit type
AC 50 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.8...1.1 Uc -40...140 °F (-40...60 °C) operational AC 50 Hz0.3...0.6 Uc -40...158 °F (-40...70 °C) drop-out AC 50 Hz1...1.1 Uc 140...158 °F (60...70 °C) operational AC 50 Hz
Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor closed 15 Gn for 11 ms) Shocks contactor open 10 Gn for 11 ms)