The LC1D40004G6 is a non-reversing IEC contactor designed for demanding applications, offering a 60A resistive, 4-pole configuration.
Product ModelLC1D40004G6
Product ID32116
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureDesigned for demanding applications with a non-reversing, 60A resistive, 4-pole configuration.
2
FeatureIdeal for use in a wide range of industrial settings due to its robust design.
3
FeatureFeatures a 120VAC coil voltage for efficient operation.
4
FeatureCompliant with IEC standards for reliability and performance.
5
FeatureAvailable in a chassis mount or DIN rail mounting type for flexibility.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1AC-3AC-3eAC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit 690 V AC 25...400 Hz
[Ie] rated operational current
60 A (at <140 °F (60 °C)) at 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
120 V AC 60 Hz
compatibility code
LC1D
Pole contact composition
4 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for control circuit40 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
140 A AC for control circuit conforming to IEC 60947-5-1800 A at 440 V AC for power circuit conforming to IEC 60947
Rated breaking capacity
800 kA at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for control circuit conforming to IEC 60947-5-180 A at 690 V coordination type 1 for power circuit80 A at 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole
5.4 W AC-12.4 W AC-3
[Ui] rated insulation voltage
Control circuit 600 V CSAControl circuit 600 V ULPower circuit 600 V CSAPower circuit 600 V ULControl circuit 690 V IEC 60947-4-1Power circuit 690 V IEC 60947-4-1
Overvoltage category
III
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
15000000 cycles
Control circuit type
AC 60 Hz standard
Coil technology
Without built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits
0.3...0.6 Uc 140 °F (60 °C) drop-out AC 50/60 Hz0.85...1.1 Uc 140 °F (60 °C) operational AC 60 Hz
1.5 ms on de-energisation between NC and NO contacts1.5 ms on energisation between NC and NO contacts
Mounting Support
PlateRail
Standards
CSA C22.2 No 14EN/IEC 60947-5-1UL 508EN/IEC 60947-4-1
Product Certifications
CSADNVGLBVULCCCRINALROS (Lloyds register of shipping)UKCA
IP degree of protection
IP2X VDE 0106
Protective treatment
THIEC 60068-2-30
Permissible ambient air temperature around the device
23...140 °F (-5...60 °C)-40...158 °F (-40...70 °C) at Uc
Operating altitude
9842.52 ft (3000 m) without derating
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms) Vibrations contactor opened 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz)