The LC1D40008N7 TeSys Deca Contactor is a reliable and efficient solution for AC-1 <= 440 V, 60 A, and 415 V AC 50/60 Hz applications.
Product ModelLC1D40008N7
Product ID31956
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureReliable operation in AC-1 <= 440 V, 60 A, and 415 V AC 50/60 Hz applications.
2
FeatureEfficient power consumption of 4…5 W at 50/60 Hz.
3
Fast switching times4...19 ms opening and 12...26 ms closing.
4
High cycle durability3600 cycles per hour at 60 °C.
5
FeatureEasy installation with screw clamp terminals 2 1…2.5 mm².
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 HzPower circuit <= 300 V DC
[Ie] rated operational current
60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
415 V AC 50/60 Hz
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
Without
[Ith] conventional free air thermal current
60 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
320 A 104 °F (40 °C) - 10 s for power circuit720 A 104 °F (40 °C) - 1 s for power circuit72 A 104 °F (40 °C) - 10 min for power circuit165 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating
80 A gG at <= 690 V coordination type 1 for power circuit80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole
5.4 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULPower circuit 690 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6 Mcycles
Electrical durability
1.4 Mcycles 60 A AC-1 <= 440 V
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40...158 °F (-40...70 °C) drop-out AC 50/60 Hz0.8...1.1 Uc -40...140 °F (-40...60 °C) operational AC 50 Hz0.85...1.1 Uc -40...140 °F (-40...60 °C) operational AC 60 Hz1...1.1 Uc 140...158 °F (60...70 °C) operational AC 50/60 Hz
Inrush power in VA
140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))160 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
Product Certifications
GOSTULLROS (Lloyds register of shipping)CSARINADNVBVGLCCC
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-40...140 °F (-40...60 °C)140...158 °F (60...70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms) Vibrations contactor opened 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz)