The LC1D40008D7 TeSys Deca Contactor is a reliable solution for non-inductive load applications, offering high performance and durability.
Product ModelLC1D40008D7
Product ID31938
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-performance contactor for non-inductive loads
2
FeatureOperating voltage up to 440V AC and current rating up to 60A
3
Feature42V AC coil for efficient operation
4
Feature3600 cycles/hour operating rate for continuous use
5
Feature140°F (60°C) operating temperature for robust performance
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 1000 V AC 25...400 Hz
[Ie] rated operational current
60 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
42 V AC 50/60 Hz
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
With
[Ith] conventional free air thermal current
60 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
800 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
320 A 104 °F (40 °C) - 10 s for power circuit720 A 104 °F (40 °C) - 1 s for power circuit72 A 104 °F (40 °C) - 10 min for power circuit165 A 104 °F (40 °C) - 1 min for power circuit
Associated fuse rating
80 A gG at <= 690 V coordination type 1 for power circuit80 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 60 A 50 Hz for power circuit
Power dissipation per pole
5.4 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULPower circuit 690 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6 Mcycles
Electrical durability
1.4 Mcycles 60 A AC-1 <= 440 V
Control circuit type
AC 50/60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40...158 °F (-40...70 °C) drop-out AC 50/60 Hz0.8...1.1 Uc -40...140 °F (-40...60 °C) operational AC 50 Hz0.85...1.1 Uc -40...140 °F (-40...60 °C) operational AC 60 Hz1...1.1 Uc 140...158 °F (60...70 °C) operational AC 50/60 Hz
Inrush power in VA
245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))15 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 60947-4-1UL 60947-5-1CSA C22.2 No 60947-4-1CSA C22.2 No 60947-5-1GB/T 14048.4
Product Certifications
ULCSACCCEACUKCACBEU-RO-MR by DNV-GL
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
Permissible ambient air temperature around the device
-40...140 °F (-40...60 °C)140...158 °F (60...70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Shocks contactor open 8 Gn for 11 ms) Shocks contactor closed 10 Gn for 11 ms) Vibrations contactor opened 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz)
Height
5.0000000000 in (127 mm)
Width
3.3 in (85 mm)
Depth
4.9 in (125 mm)
Net Weight
3.17 lb(US) (1.44 kg)
LC1D40008D7 TeSys Deca Contactor | Schneider Electric | INDPRT