4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuitScrew connector - rigid without cable end 1 0.5...2.5 mm² AWG 14 control circuit4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuitScrew connector - rigid 2 0.5...1 mm² AWG 17 control circuitScrew connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuitScrew connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuitScrew connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
marking
CE
Operating position
Vertical +/- 10 degree
Height
12.4 in (314 mm)
Width
1.8 in (45 mm)
Depth
6.7 in (170 mm)
Net Weight
1.08 lb(US) (0.49 kg)
Motor power range AC-3
7...11 kW 200...240 V 3 phase15...25 kW 380...440 V 3 phase
Motor starter type
Soft starter
Electromagnetic compatibility
Conducted and radiated emissions level B CISPR 11Conducted and radiated emissions level B IEC 60947-4-2Damped oscillating waves level 3 IEC 61000-4-12Electrostatic discharge level 3 IEC 61000-4-2EMC immunity EN 50082-1EMC immunity level B EN 50082-2Harmonics level 3 IEC 1000-3-2Harmonics level 3 IEC 1000-3-4Immunity to electrical transients level 4 IEC 61000-4-4Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3Voltage/current impulse level 3 IEC 61000-4-5Conducted and radiated emissions level 3 IEC 61000-4-6Immunity to conducted interference caused by radio-electrical fields level 4 IEC 61000-4-11
Standards
EN/IEC 60947-4-2
Product Certifications
ULCCCCSAC-tick
IP Degree of Protection
IP20
Pollution degree
2 EN/IEC 60947-4-2
Vibration resistance
1 gn 13...150 Hz)EN/IEC 60068-2-61.5 mm peak to peak 3...13 Hz)EN/IEC 60068-2-6
Shock resistance
15 gn 11 ms EN/IEC 60068-2-27
Relative humidity
5...95 % without condensation or dripping water EN/IEC 60068-2-3
Ambient air temperature for operation
14...104 °F (-10...40 °C) without derating)104...122 °F (40...50 °C) with current derating of 2 % per °C)
Ambient air temperature for storage
-13...158 °F (-25...70 °C) EN/IEC 60947-4-2
Operating altitude
<= 3280.84 ft (1000 m) without derating> 3280.84 ft (1000 m) with current derating of 2.2 % per additional 100 m