Reliable 4-pole magnetic contactor with 200A AC-1 rated current, suitable for direct on-line and full-voltage non-reversing applications.
Product ModelLC1D115004M7
Product ID31442
Stock on Request
Last updated: 8/29/2026
Key Features
1
Feature-
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1AC-3AC-3eAC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 1000 V AC 25...400 HzPower circuit <= 460 V DC
[Ie] rated operational current
200 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
220 V AC 50/60 Hz
compatibility code
LC1D
Pole contact composition
4 NO
Protective cover
With
[Ith] conventional free air thermal current
200 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
1260 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
250 A 104 °F (40 °C) - 10 min for power circuit550 A 104 °F (40 °C) - 1 min for power circuit950 A 104 °F (40 °C) - 10 s for power circuit1100 A 104 °F (40 °C) - 1 s for power circuit
Associated fuse rating
250 A gG at <= 690 V coordination type 1 for power circuit200 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole
24 W AC-1
[Ui] rated insulation voltage
Power circuit 600 V CSAPower circuit 600 V ULPower circuit 1000 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV IEC 60947
Safety reliability level
B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 508
Product Certifications
CCCRINAGOSTULCSALROS (Lloyds register of shipping)BVGLDNVUKCA
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device
-40...140 °F (-40...60 °C)140...158 °F (60...70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor closed 15 Gn for 11 ms) Shocks contactor open 6 Gn for 11 ms)
Height
6.2 in (158 mm)
Width
5.9 in (150 mm)
Depth
5.2 in (132 mm)
Net Weight
6.31 lb(US) (2.86 kg)
LC1D115004M7 - TeSys Deca Magnetic Contactor by Schneider Electric | INDSLT