Power circuit 690 V IEC 60947-4-1Signalling circuit 690 V IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Overvoltage category
III
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for signalling circuit25 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
250 A at 440 V for power circuit conforming to IEC 60947140 A AC for signalling circuit conforming to IEC 60947-5-1250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-140 A gG at <= 690 V coordination type 1 for power circuit25 A gG at <= 690 V coordination type 2 for power circuit
Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor open 10 Gn for 11 ms) Shocks contactor closed 15 Gn for 11 ms)