The LC1D098ED TeSys Deca non-reversing contactor is a reliable and efficient solution for 20A resistive applications with 4 poles and a 48VDC coil.
Product ModelLC1D098ED
Product ID31124
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureReliable performance in 20A resistive applications.
2
Feature4-pole configuration for versatile electrical control systems.
3
Feature2 NO and 2 NC contacts for precise control.
4
Feature48VDC coil for efficient operation.
5
FeatureNon-reversing design ensures consistent and reliable switching.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Utilisation category
AC-1AC-3AC-3eAC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 HzPower circuit <= 250 V DC
[Ie] rated operational current
25 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
48 V DC
compatibility code
LC1D
Pole contact composition
2 NO + 2 NC
Protective cover
With
[Ith] conventional free air thermal current
20 A (at 140 °F (60 °C)) for power circuit10 A (at 140 °F (60 °C)) for signalling circuit
Irms rated making capacity
250 A at 440 V for power circuit conforming to IEC 60947140 A AC for signalling circuit conforming to IEC 60947-5-1250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
105 A 104 °F (40 °C) - 10 s for power circuit210 A 104 °F (40 °C) - 1 s for power circuit30 A 104 °F (40 °C) - 10 min for power circuit61 A 104 °F (40 °C) - 1 min for power circuit100 A - 1 s for signalling circuit120 A - 500 ms for signalling circuit140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-125 A gG at <= 690 V coordination type 1 for power circuit20 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole
1.56 W AC-1
[Ui] rated insulation voltage
Power circuit 690 V IEC 60947-4-1Power circuit 600 V CSAPower circuit 600 V ULSignalling circuit 690 V IEC 60947-1Signalling circuit 600 V CSASignalling circuit 600 V UL
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
1.5 ms on de-energisation between NC and NO contact1.5 ms on energisation between NC and NO contact
Mounting Support
RailPlate
Standards
CSA C22.2 No 14EN 60947-4-1EN 60947-5-1IEC 60947-4-1IEC 60947-5-1UL 60947-4-1IEC 60335-1:Clause 30.2IEC 60335-2-40:Annex JJUL 60335-2-40:Annex JJCSA C22.2 No 60947-4-1
Product Certifications
ULCCCCSAMarineUKCAEACCB Scheme
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device
-40...140 °F (-40...60 °C)140...158 °F (60...70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness