19 W in transient state4 W at full load and at end of starting
Assembly style
With heat sink
Function Available
Integrated bypass
Supply voltage limits
99...528 V
Supply frequency
50...60 Hz - 5...5 %
Network Frequency
47.5...63 Hz
Output voltage
<= power supply voltage
[Uc] control circuit voltage
110 V AC +/- 10 % 30 mA24 V AC/DC +/- 10 % 25 mA240 V AC +/- 10 % 65 mA
Starting time
1 s / 1005 s / 20Adjustable from 1 to 5 s
Starting torque
30...80 % of starting torque of motor connected directly on the line supply
Discrete output current
2 A DC-133 A AC-15
Tightening torque
7.08 lbf.in (0.8 N.m)
Electrical connection
Cage type connector - rigid 1 2.5 mm² AWG 14 control circuitCage type connector - rigid with cable end 1 2.5 mm² AWG 14 power circuitCage type connector - rigid without cable end 2 1 mm² AWG 17 control circuitCage type connector - rigid without cable end 2 1 mm² AWG 17 power circuitCage type connector - flexible with cable end 1 2.5 mm² AWG 14 control circuitCage type connector - flexible with cable end 1 2.5 mm² AWG 14 power circuitCage type connector - flexible without cable end 1 2.5 mm² AWG 14 control circuitCage type connector - flexible without cable end 1 2.5 mm² AWG 14 power circuitCage type connector - flexible with cable end 2 0.75 mm² AWG 18 control circuitCage type connector - flexible with cable end 2 0.75 mm² AWG 18 power circuitCage type connector - flexible without cable end 2 1 mm² AWG 17 control circuitCage type connector - flexible without cable end 2 1 mm² AWG 17 power circuit
marking
CE
Operating position
Vertical +/- 10 degree
Height
3.9 in (100 mm)
Width
0.9 in (23 mm)
Depth
3.9 in (100 mm)
Net Weight
0.35 lb(US) (0.16 kg)
compatibility code
ATS01N1
Motor power range AC-3
0...0.5 kW 200...240 V 1 phase0...0.5 kW 200...240 V 3 phase0.55...1 kW 200...240 V 3 phase1.1...2 kW 380...440 V 3 phase
Motor starter type
Soft starter
Electromagnetic compatibility
Conducted and radiated emissions level B CISPR 11Conducted and radiated emissions level B IEC 60947-4-2Damped oscillating waves level 3 IEC 61000-4-12Electrostatic discharge level 3 IEC 61000-4-2EMC immunity level 3 EN 50082-1EMC immunity level B EN 50082-2Harmonics level 3 IEC 1000-3-2Harmonics level 3 IEC 1000-3-4Immunity to conducted interference caused by radio-electrical fields level 3 IEC 61000-4-6Immunity to electrical transients level 4 IEC 61000-4-4Immunity to radiated radio-electrical interference level 3 IEC 61000-4-3Micro-cuts and voltage fluctuation IEC 61000-4-11Voltage/current impulse level 3 IEC 61000-4-5
Standards
EN/IEC 60947-4-2
Product Certifications
CSAGOSTC-tickULCCC
IP Degree of Protection
IP20
Pollution degree
2 EN/IEC 60947-4-2
Vibration resistance
1 gn 13...150 Hz)EN/IEC 60068-2-61.5 mm peak to peak 3...13 Hz)EN/IEC 60068-2-6
Shock resistance
15 gn 11 ms EN/IEC 60068-2-27
Relative humidity
5...95 % without condensation or dripping water EN/IEC 60068-2-3
Ambient air temperature for operation
14...104 °F (-10...40 °C) without derating)104...122 °F (40...50 °C) with current derating of 2 % per °C)
Ambient air temperature for storage
-13...158 °F (-25...70 °C) EN/IEC 60947-4-2
Operating altitude
<= 3280.84 ft (1000 m) without derating> 3280.84 ft (1000 m) with current derating of 2.2 % per additional 100 m