The GV2ME22 TeSys Deca Manual Starter and Protector provides thermal-magnetic circuit protection and manual motor control in a compact unit.
Product ModelGV2ME22
Product ID30467
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureCompact design for easy installation
2
FeatureThermal-magnetic circuit protection for reliable motor control
3
FeatureManual isolation and motor control in one unit
4
FeatureSuitable for AC-3 applications conforming to IEC 60947-4-1
5
FeatureHigh durability with 100,000 cycles of mechanical and electrical operation
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys Deca
Product name
TeSys GV2
Product or Component Type
Motor circuit breaker
Device short name
GV2ME
Device Application
Motor protection
Trip unit technology
Thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A IEC 60947-2AC-3 IEC 60947-4-1AC-3e IEC 60947-4-1
Network frequency
50/60 Hz IEC 60947-4-1
Motor power kW
11 kW 400/415 V AC 50/60 Hz15 kW 500 V AC 50/60 Hz
Breaking capacity
50 kA Icu 230/240 V AC 50/60 Hz IEC 60947-215 kA Icu 400/415 V AC 50/60 Hz IEC 60947-26 kA Icu 440 V AC 50/60 Hz IEC 60947-24 kA Icu 500 V AC 50/60 Hz IEC 60947-23 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-240 % 400/415 V AC 50/60 Hz IEC 60947-250 % 440 V AC 50/60 Hz IEC 60947-275 % 500 V AC 50/60 Hz IEC 60947-275 % 690 V AC 50/60 Hz IEC 60947-2
Control Type
Push-button
Line Rated Current
25 A
Thermal protection adjustment range
20...25 A IEC 60947-4-1
Magnetic tripping current
388.3 A
[Ith] conventional free air thermal current
25 A IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
Phase failure sensitivity
Yes IEC 60947-4-1
Suitability for isolation
Yes IEC 60947-1
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles AC-3 415 V In100000 cycles AC-3e 415 V In
Rated duty
Continuous IEC 60947-4-1
Tightening torque
15.05 lbf.in (1.7 N.m) screw clamp terminal
Fixing mode
35 mm symmetrical DIN rail clippedPanel screwed with adaptor plate)