The GV2ME216 is a thermal-magnetic motor protection circuit breaker designed for AC-3 applications, ensuring continuous operation and safety.
Product ModelGV2ME216
Product ID30466
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureDesigned for AC-3 applications, conforming to IEC 60947-4-1.
2
FeatureEnsures continuous operation and safety with its thermal-magnetic circuit protection.
3
FeatureIdeal for use in industrial settings requiring reliable motor protection.
4
FeatureCompliant with IEC 60947-4-1 standards for AC-3 utilization categories.
5
FeatureCompact design for easy installation on 35 mm symmetrical DIN rail.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys Deca
Product name
TeSys GV2
Product or Component Type
Motor circuit breaker
Device short name
GV2ME
Device Application
Motor protection
Trip unit technology
Thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A IEC 60947-2AC-3 IEC 60947-4-1AC-3e IEC 60947-4-1
Network frequency
50/60 Hz IEC 60947-4-1
Motor power kW
9 kW 400/415 V AC 50/60 Hz11 kW 500 V AC 50/60 Hz18.5 kW 690 V AC 50/60 Hz
Breaking capacity
50 kA Icu 230/240 V AC 50/60 Hz IEC 60947-215 kA Icu 400/415 V AC 50/60 Hz IEC 60947-26 kA Icu 440 V AC 50/60 Hz IEC 60947-24 kA Icu 500 V AC 50/60 Hz IEC 60947-23 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-240 % 400/415 V AC 50/60 Hz IEC 60947-250 % 440 V AC 50/60 Hz IEC 60947-275 % 500 V AC 50/60 Hz IEC 60947-275 % 690 V AC 50/60 Hz IEC 60947-2
Control Type
Push-button
Line Rated Current
23 A
Thermal protection adjustment range
17...23 A IEC 60947-4-1
Magnetic tripping current
341 A
[Ith] conventional free air thermal current
23 A IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
Phase failure sensitivity
Yes IEC 60947-4-1
Suitability for isolation
Yes IEC 60947-1
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles AC-3 415 V In100000 cycles AC-3e 415 V In
Rated duty
Continuous IEC 60947-4-1
Fixing mode
35 mm symmetrical DIN rail clippedPanel screwed with adaptor plate)