{ DescriptionEfficient Motor Protection: The GV2ME06 offers robust thermal-magnetic protection, ensuring your motors operate safely and efficiently. }
2
{ DescriptionVersatile Mounting Options: Easily mount the GV2ME06 on rails or panels, providing flexibility in your electrical setup. }
3
{ DescriptionHigh Breaking Capacity: With a breaking capacity of 100 kA, the GV2ME06 can handle high short-circuit currents, making it ideal for demanding applications. }
4
{ DescriptionUser-Friendly Control: The push-button control makes it easy to operate and maintain the circuit breaker, reducing downtime and increasing productivity. }
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys Deca
Product name
TeSys GV2
Product or Component Type
Motor circuit breaker
Device short name
GV2ME
Device Application
Motor protection
Trip unit technology
Thermal-magnetic
{ DescriptionCompliance with International Standards: The GV2ME06 meets IEC 60947-2 and other international standards, ensuring compliance and reliability in your electrical systems. }
Poles description
3P
Network type
AC
Utilisation category
Category A IEC 60947-2AC-3 IEC 60947-4-1AC-3e IEC 60947-4-1
Network frequency
50/60 Hz IEC 60947-4-1
Motor power kW
0.37 kW 400/415 V AC 50/60 Hz0.55 kW 400/415 V AC 50/60 Hz0.37 kW 500 V AC 50/60 Hz0.55 kW 500 V AC 50/60 Hz0.75 kW 500 V AC 50/60 Hz0.75 kW 690 V AC 50/60 Hz1.1 kW 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2100 kA Icu 440 V AC 50/60 Hz IEC 60947-2100 kA Icu 500 V AC 50/60 Hz IEC 60947-2100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-2100 % 400/415 V AC 50/60 Hz IEC 60947-2100 % 440 V AC 50/60 Hz IEC 60947-2100 % 500 V AC 50/60 Hz IEC 60947-2100 % 690 V AC 50/60 Hz IEC 60947-2
Control Type
Push-button
Line Rated Current
1.6 A
Thermal protection adjustment range
1...1.6 A IEC 60947-4-1
Magnetic tripping current
26.2 A
[Ith] conventional free air thermal current
1.6 A IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
Phase failure sensitivity
Yes IEC 60947-4-1
Suitability for isolation
Yes IEC 60947-1
Power dissipation per pole
2.5 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles AC-3 415 V In100000 cycles AC-3e 415 V In
Rated duty
Continuous IEC 60947-4-1
Tightening torque
15.05 lbf.in (1.7 N.m) screw clamp terminal
Fixing mode
35 mm symmetrical DIN rail clippedPanel screwed with adaptor plate)