The Schneider Electric GV2LE20 TeSys GV2 Circuit Breaker is a magnetic motor circuit breaker designed for reliable and efficient protection of motors.
Product ModelGV2LE20
Product ID30186
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureRobust magnetic circuit protection for motors.
2
FeatureEasy installation with screw clamp terminals.
3
FeatureIdeal for various applications requiring high reliability and efficiency.
4
FeatureAdditional features like fault indicators and undervoltage trips available separately.
5
FeatureMount multiple starters using a busbar system for enhanced functionality.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys Deca
Product name
TeSys GV2
Product or Component Type
Motor circuit breaker
Device short name
GV2LE
Device Application
Motor protection
Trip unit technology
Magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A IEC 60947-2AC-3 IEC 60947-4-1AC-3e IEC 60947-4-1
Network frequency
50/60 Hz IEC 60947-2
Motor power kW
7.5 kW 400/415 V AC 50/60 Hz9 kW 500 V AC 50/60 Hz15 kW 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-215 kA Icu 400/415 V AC 50/60 Hz IEC 60947-28 kA Icu 440 V AC 50/60 Hz IEC 60947-26 kA Icu 500 V AC 50/60 Hz IEC 60947-23 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-250 % 400/415 V AC 50/60 Hz IEC 60947-250 % 440 V AC 50/60 Hz IEC 60947-275 % 500 V AC 50/60 Hz IEC 60947-275 % 690 V AC 50/60 Hz IEC 60947-2
Control Type
Toggle
Line Rated Current
18 A
Thermal protection adjustment range
13...18 A IEC 60947-4-1
Magnetic tripping current
341 A
[Ith] conventional free air thermal current
18 A IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
Suitability for isolation
Yes IEC 60947-1
Power dissipation per pole
1.8 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles AC-3 415 V In100000 cycles AC-3e 415 V In
Rated duty
Continuous IEC 60947-4-1
Tightening torque
15.05 lbf.in (1.7 N.m) screw clamp terminal
Fixing mode
35 mm symmetrical DIN rail clippedPanel screwed with adaptor plate)
Mounting position
HorizontalVertical
Width
1.8 in (45 mm)
Height
3.5 in (89 mm)
Depth
3.09 in (78.5 mm)
Net Weight
0.73 lb(US) (0.33 kg)
color
Dark grey
Standards
EN/IEC 60947-2EN/IEC 60947-4-1UL 60947-4-1CSA C22.2 No 60947-4-1IEC/EN 60335-2-40:Annex JJ