The Schneider Electric GV2LE16 is a magnetic circuit breaker designed for 3-phase motor applications, offering reliable protection and high breaking capacity.
Product ModelGV2LE16
Product ID30185
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureIdeal for 3-phase motor applications up to 5.5 kW at 400V.
2
FeatureProvides magnetic protection with a tripping level at 13xIn.
3
FeatureHigh breaking capacity of 15kA@400V for reliable operation.
4
FeatureGuaranteed for 100,000 start-stop cycles AC-3.
5
FeatureScrew clamp terminals for easy installation and maintenance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range
TeSys Deca
Product name
TeSys GV2
Product or Component Type
Motor circuit breaker
Device short name
GV2LE
Device Application
Motor protection
Trip unit technology
Magnetic
Poles description
3P
Network type
AC
Utilisation category
Category A IEC 60947-2AC-3 IEC 60947-4-1AC-3e IEC 60947-4-1
Network frequency
50/60 Hz IEC 60947-2
Motor power kW
5.5 kW 400/415 V AC 50/60 Hz7.5 kW 500 V AC 50/60 Hz9 kW 690 V AC 50/60 Hz11 kW 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-215 kA Icu 400/415 V AC 50/60 Hz IEC 60947-28 kA Icu 440 V AC 50/60 Hz IEC 60947-26 kA Icu 500 V AC 50/60 Hz IEC 60947-23 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-250 % 400/415 V AC 50/60 Hz IEC 60947-250 % 440 V AC 50/60 Hz IEC 60947-275 % 500 V AC 50/60 Hz IEC 60947-275 % 690 V AC 50/60 Hz IEC 60947-2
Control Type
Toggle
Line Rated Current
14 A
Thermal protection adjustment range
9...14 A IEC 60947-4-1
Magnetic tripping current
253.4 A
[Ith] conventional free air thermal current
14 A IEC 60947-4-1
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
Suitability for isolation
Yes IEC 60947-1
Power dissipation per pole
1.8 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles AC-3 415 V In100000 cycles AC-3e 415 V In
Rated duty
Continuous IEC 60947-4-1
Tightening torque
15.05 lbf.in (1.7 N.m) screw clamp terminal
Fixing mode
35 mm symmetrical DIN rail clippedPanel screwed with adaptor plate)
Mounting position
HorizontalVertical
Width
1.8 in (45 mm)
Height
3.5 in (89 mm)
Depth
3.09 in (78.5 mm)
Net Weight
0.73 lb(US) (0.33 kg)
color
Dark grey
Standards
EN/IEC 60947-2EN/IEC 60947-4-1UL 60947-4-1CSA C22.2 No 60947-4-1IEC/EN 60335-2-40:Annex JJ
Product Certifications
CCCULCSAEACLROS (Lloyds register of shipping)BVRINADNV-GLUKCAIECEE CB Scheme
IK degree of protection
IK04
IP degree of protection
IP20 IEC 60529
Climatic withstand
IACS E10
Ambient Air Temperature for Storage
-40...176 °F (-40...80 °C)
Fire resistance
1760 °F (960 °C) IEC 60695-2-11
Ambient air temperature for operation
-4...140 °F (-20...60 °C)
Mechanical robustness
Shocks 30 Gn for 11 msVibrations 5 Gn, 5...150 Hz
Operating altitude
6561.68 ft (2000 m)
Schneider Electric GV2LE16 Magnetic Circuit Breaker | Augto.com | INDSLT