The BMXCPS3522H is a redundant power supply module designed for the Modicon X80, ensuring reliable and efficient power distribution in industrial applications.
Product ModelBMXCPS3522H
Product ID30058
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureEnhanced reliability with redundant power supply
2
FeatureCompliant with 100-150V primary voltage limits
3
FeatureEfficient power distribution for industrial applications
4
FeatureDesigned for the Modicon X80 series
5
FeatureCybersecure operation for improved risk management
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Modicon X80
Product or Component Type
Power supply module
backplane compatibility
All backplane
Product Specific Application
For severe environments
advanced diagnostics available via network
Temperature sensingRedundancy informationRedundancy testUptime durationRemaining lifetime
Primary Voltage
125 V
Supply circuit type
DC
Secondary power
18 W 3.3 V DC -13...158 °F (-25...70 °C) I/O module logic power supply40 W 24 V DC -13...158 °F (-25...70 °C) I/O module power supply and processor if 3.3 V not loaded
1500 V primary/secondary I/O module logic power supply1500 V primary/secondary I/O module power supply and processor2300 V primary/secondary sensor power supply1500 V primary/ground
IP Degree of Protection
IP20
Directives
2014/35/EU - low voltage directive2014/30/EU - electromagnetic compatibility
Product certifications
CEULCSARCMEACMerchant Navy
Standards
EN 61131-2EN/IEC 61010-2-201UL 61010-2-201CSA C22.2 No 61010-2-201IACS E10EN/IEC 61000-6-5, interface type 1 and type 2EN/IEC 61850-3, location G
Environmental characteristic
Gas resistant class Gx ISA S71.04Gas resistant class 3C4 IEC 60721-3-3Dust resistant class 3S4 IEC 60721-3-3Sand resistant class 3S4 IEC 60721-3-3Salt resistant level 2 IEC 68252Mold growth resistant class 3B2 IEC 60721-3-3Fungal spore resistant class 3B2 IEC 60721-3-3Hazardous location class I division 2
Ambient Air Temperature for Storage
-40...185 °F (-40...85 °C)
Ambient Air Temperature for Operation
-13...158 °F (-25...70 °C)
Relative humidity
10...95 % without condensation
Protective treatment
Conformal coating
Redundant Power Supply Module BMXCPS3522H by Schneider Electric | INDSLT