The Schneider Electric BMXCPS2010 is a versatile power supply module for Modicon X80 systems, offering a wide voltage range and robust protection features.
Product ModelBMXCPS2010
Product ID30052
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureWide voltage range of 18 to 31.2 V DC ensures adaptability to various power conditions.
2
FeatureRobust protection features including internal fuse, overload, overvoltage, and short-circuit protection.
3
FeatureDual-output configuration with 16.8 W at 24 V DC for I/O module power supply and processor, and 8.3 W at 3.3 V DC for I/O module logic power supply.
4
FeatureEfficient design with a maximum inrush current of 30 A at 24 V, ensuring stable power supply during operation.
5
Feature
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Modicon X80
Product or Component Type
Power supply module
backplane compatibility
Not compatible with BMEXBP..02
Primary Voltage
24 V isolated
Supply circuit type
DC
Secondary power
16.8 W 24 V DC I/O module power supply and processor8.3 W 3.3 V DC I/O module logic power supply
Ideal for industrial environments with high levels of electrical insulation and resistance to mechanical stresses.
Primary voltage limit
18...31.2 V
Input current
1 A 24 V
Inrush current
30 A 24 V
I²t on activation
0.6 A².s 24 V
It on activation
0.15 A.s 24 V
MTBF reliability
4886000 H
Protection type
Internal fuse not accessible primary circuitOverload protection secondary circuit, 24 V sensor power supplyOvervoltage protection secondary circuit, 24 V sensor power supplyShort-circuit protection secondary circuit, 24 V sensor power supply
Current at secondary voltage
0.7 A 24 V DC I/O module power supply and processor2.5 A 3.3 V DC I/O module logic power supply
Maximum power dissipation in W
8.5 W
Status LED
1 LED (Green) rack voltage OK
Control Type
RESET push-button cold restart
Electrical connection
1 connector 2 alarm relay1 connector 5 line supply, protective earth, 24 V DC input sensor
Maximum cable distance between devices
65.6 ft (20 m) power supply cable copper 0.002 in² (1.5 mm²)98.4 ft (30 m) power supply cable copper 0.004 in² (2.5 mm²)