31.8 A 380 V AC voltage inputs continuous)27.9 A 500 V AC voltage inputs continuous)43.1 A 380 V AC voltage inputs transient for 60 s)36.3 A 500 V AC voltage inputs transient for 60 s)
Input power
13.5 kW 380...500 V AC voltage inputs continuous)20.3 kW 380...500 V AC voltage inputs transient for 60 s)
Maximum DC bus voltage
300...880 V DC
Output Current
25.9 A 380 V AC continuous)23.2 A 500 V AC continuous)36.5 A 380 V AC transient for 60 s)29.7 A 500 V AC transient for 60 s)
Width
4.1 in (105 mm)
Height
15.7 in (399 mm)
Depth
9.3 in (235 mm)
Net Weight
25.4 lb(US) (11.5 kg)
Standards
IEC 61800-3IEC 61800-5-1
Product Certifications
cUL
Ambient air temperature for operation
14...122 °F (-10...50 °C) without derating122...140 °F (50...60 °C) with derating factor
Ambient Air Temperature for Storage
-40...158 °F (-40...70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating3280.84...9842.52 ft (1000...3000 m) with power derating 1 % per 100 m
Operating position
Vertical or horizontal position
Type of cooling
Fan
Environmental characteristic
Chemical pollution resistance class 3C3 IEC 60721-3-3Dust pollution resistance class 3S2 IEC 60721-3-3
Pollution degree
2 IEC 61800-5-1
Schneider Electric ATVRD15N4 Regenerative Unit | INDSLT