The 140DDI84100C discrete input module from Schneider Electric provides 16 inputs with a voltage range of 10 to 60 V DC, making it suitable for various industrial applications.
Product Model140DDI84100C
Product ID29409
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureReliable Performance
2
FeatureWide Voltage Range
3
FeatureHigh Channel Count
4
FeaturePositive Logic Input
5
FeatureIndustrial-Grade Quality
6
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Modicon Quantum automation platform
Product or Component Type
Dc discrete input modules
Discrete input number
16
Group of channels
8
Logic input
Positive (sink)
input voltage limits
10...60 V
FeatureReliable Performance
7
FeatureWide Voltage Range
8
FeatureHigh Channel Count
9
FeaturePositive Logic Input
10
FeatureIndustrial-Grade Quality
Input voltage
12 V 5...10 mA DC24 V 6...30 mA DC48 V 2...15 mA DC60 V 1...5 mA DC
Voltage state 1 guaranteed
11...24 V 24 V +/- 20 %34...48 V 48 V +/- 20 %45...60 V 60 V +/- 20 %9...12 V 12 V +/- 5 %
Voltage state 0 guaranteed
0...1.8 V 12 V +/- 5 %0...10 V 48 V +/- 20 %0...5 V 24 V +/- 20 %0...9 V 60 V +/- 20 %
Absolute maximum voltage
75 V
Addressing requirement
1 input word
Response Time
4 ms from state 0 to state 14 ms from state 1 to state 0
Switching frequency
<= 100 Hz
Isolation between group and bus
2500 Vrms DC for 1 minute
Isolation between group
700 Vrms DC for 1 minute
Power dissipation
1 W + (0.62 x number of points on)
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green) for external fault detected (F) 1 LED (red) for input status 16 LEDs (green)
Bus current requirement
200 mA
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
CSA C22.2 No 142UL 508
Product Certifications
FM Class 1 Division 2C-tick
Resistance to electrostatic discharge
4 kV contact IEC 801-28 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80...2000 MHz IEC 801-3
Ambient Air Temperature for Operation
32...140 °F (0...60 °C)
Ambient Air Temperature for Storage
-40...185 °F (-40...85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)
Discrete Input Module Modicon Quantum - 16 I - 10..60 V DC | INDSLT