The Altivar Process ATV630U75Y6 is a 7.5 HP variable speed drive suitable for 500 to 690V applications, featuring embedded power measurement and energy dashboard.
Product ModelATV630U75Y6
Product ID29109
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureEnergy saving with embedded power measurement and energy dashboard.
2
FeatureAdvanced asset monitoring and protection capabilities.
3
FeatureMercury-free design for environmental sustainability.
4
FeatureCompliance with EU RoHS Directive and China RoHS Regulation.
5
FeatureIdeal for applications requiring precise motor control.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Altivar Process ATV600
Product or Component Type
Variable speed drive
Product Specific Application
Process and utilities
Device short name
ATV630
Variant
Standard version
Product destination
Asynchronous motorsSynchronous motors
EMC filter
Integrated 82.02 ft (25 m) IEC 61800-3 category C3
IP degree of protection
IP21IEC 60529IP00IEC 61800-5-1
[Us] rated supply voltage
500...690 V - 15...10 %
Type of cooling
Forced convection
Supply frequency
50...60 Hz - 5...5 %
Motor power kW
5.5 kW 500 V normal duty)
Maximum Horse Power Rating
7.5 hp 600 V heavy duty7.5 hp 500 V normal duty
Line current
7.7 A 600 V heavy duty)10.4 A 500 V normal duty)
Prospective line Isc
70 kA
Apparent power
8 kVA 600 V heavy duty)12.5 kVA 690 V normal duty)
Continuous output current
9.5 A 4 kHz heavy duty7.2 A 4 kHz heavy duty
Asynchronous motor control profile
Optimized torque modeConstant torque standardConstant torque standard
Synchronous motor control profile
Synchronous reluctance motorPermanent magnet motor
Speed drive output frequency
0.1...500 Hz
Nominal switching frequency
4 kHz
Switching frequency
4...12 kHz with derating factor2...8 kHz adjustable
Slot A communication module, PROFINETSlot A communication module, DeviceNetSlot A communication module, Modbus TCP/EtherNet/IPSlot A communication module, CANopen daisy chain RJ45Slot A communication module, CANopen SUB-D 9Slot A communication module, CANopen screw terminalsSlot A/slot B digital and analog I/O extension moduleSlot A/slot B output relay extension moduleSlot A communication module, Ethernet IP/Modbus TCP/MD-Link communication module, BACnet MS/TP communication module, Ethernet PowerlinkSlot A communication module, Profibus DP V1
Mounting Mode
Wall mount
Maximum transient current
14.3 A 60 s heavy duty)10.8 A 60 s heavy duty)
Phase
3 phase
Discrete output number
0
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mARelay outputs R1A, R1B, R1C 30 V DC 3000 mARelay outputs R2A, R2C 250 V AC 5000 mARelay outputs R2A, R2C 30 V DC 5000 mARelay outputs R3A, R3C 250 V AC 5000 mARelay outputs R3A, R3C 30 V DC 5000 mA
Output voltage
<= power supply voltage
Permissible temporary current boost
1.5 x In 60 s heavy duty)1.1 x In 60 s normal duty)
Motor slip compensation
Not available in permanent magnet motor lawCan be suppressedAdjustableAutomatic whatever the load
Acceleration and deceleration ramps
S, U or customizedLinear adjustable separately from 0.01...9999 s
Physical interface
Ethernet2-wire RS 485
Braking to standstill
By DC injection
Protection type
Safe torque off motorMotor phase break motorThermal protection driveSafe torque off driveOverheating driveOvercurrent between output phases and earth driveOverload of output voltage driveShort-circuit protection driveMotor phase break driveOvervoltages on the DC bus driveLine supply overvoltage driveLine supply undervoltage driveLine supply phase loss driveOverspeed driveBreak on the control circuit driveThermal protection motor
RJ45 on the remote graphic terminal)Modbus serialRJ45 on the remote graphic terminal)Ethernet/Modbus TCP
Data format
8 bits, configurable odd, even or no parity
Type of polarization
No impedance
Exchange mode
Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number of addresses
1...247 Modbus serial
Method of access
Slave Modbus TCP
Supply
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protectionInternal supply for digital inputs and STO 24 V DC 21...27 V), <200 mA overload and short-circuit protectionExternal supply for digital inputs 24 V DC 19...30 V), <1.25 mA overload and short-circuit protection
Local signalling
for embedded communication status 3 LEDs (dual colour) for communication module status 4 LEDs (dual colour) for presence of voltage 1 LED (red) for local diagnostic 3 LEDs
Width
9.7 in (246 mm)
Height
16.5 in (420 mm)
Depth
9.5 in (242 mm)
Net Weight
48.5 lb(US) (22 kg)
Analogue input number
3
Analogue input type
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bitsAI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bitsAI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Discrete input number
8
Discrete input type
DI7, DI8 programmable as pulse input 0...30 kHz, 24 V DC <= 30 V)
Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bitsSoftware-configurable current AQ1, AQ2 0...20 mA 10 bitsSoftware-configurable current DQ-, DQ+ 30 V DCSoftware-configurable current DQ-, DQ+ 100 mA
Sampling duration
5 ms +/- 1 ms DI5, DI6) - discrete input5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input10 ms +/- 1 ms AO1) - analog output2 ms +/- 0.5 ms DI1...DI4) - discrete input
Accuracy
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
Linearity error
AO1, AO2 +/- 0.2 % analog outputAI1, AI2, AI3 +/- 0.15 % of maximum value analog input
Relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DCRelay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V ACRelay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DCRelay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC
Isolation
Between power and control terminals
Maximum output frequency
500 kHz
Maximum Input Current per Phase
10.5 A
Quantity per Set
1
enclosure mounting
Wall mounted
Insulation resistance
> 1 MOhm 500 V DC for 1 minute to earth
Noise level
58 dB
Power dissipation in W
Forced convection 110 W 600 V 4 kHzNatural convection 88 W 500 V 4 kHz
Volume of cooling air
87178.3 Gal/hr(US) (330 m3/h)
Operating position
Vertical +/- 10 degree
Maximum THDI
<48 % with external line choke IEC 61000-3-12
Electromagnetic compatibility
Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3Electrical fast transient/burst immunity test level 4 IEC 61000-4-41.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5Conducted radio-frequency immunity test level 3 IEC 61000-4-6Electrostatic discharge immunity test level 3 IEC 61000-4-2
Pollution degree
2
Vibration resistance
1 gn 13...200 Hz)IEC 60068-2-61.5 mm peak to peak 2...13 Hz)IEC 60068-2-6
Shock resistance
15 gn 11 ms IEC 60068-2-27
Relative humidity
5...95 % without condensation IEC 60068-2-3
Ambient air temperature for operation
122...140 °F (50...60 °C) with derating factor)5...122 °F (-15...50 °C) without derating)
Ambient Air Temperature for Storage
-40...158 °F (-40...70 °C)
Operating altitude
1000...4800 m with current derating 1 % per 100 m<= 3280.84 ft (1000 m) without derating