The ATV61HU55N4 is a high-performance 3-phase AC drive designed for demanding applications in pumping and ventilation systems.
Product ModelATV61HU55N4
Product ID27805
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureRobust and efficient operation for demanding applications.
2
FeatureCompliant with industry standards for electromagnetic interference (EMI).
3
FeatureIntegrated heat sink assembly for efficient heat dissipation.
4
FeatureSupports adjustable switching frequency for optimized performance.
5
FeatureEnhanced protection against short circuits and transient currents.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Altivar 61
Product or Component Type
Variable speed drive
Product Specific Application
Pumping and ventilation machine
Component name
ATV61
Motor power kW
5.5 kW, 3 phase 380...480 V
Maximum Horse Power Rating
7.5 hp, 3 phase 380...480 V
power supply voltage
380...480 V - 15...10 %
supply number of phases
3 phase
Line current
17 A 480 V 3 phase 5.5 kW / 7.5 hp20.3 A 380 V 3 phase 5.5 kW / 7.5 hp
EMC filter
Level 3 EMC filter
Assembly style
With heat sink
Apparent power
13.4 kVA 380 V 3 phase 5.5 kW / 7.5 hp
maximum prospective line Isc
22 kA 3 phase
Maximum transient current
17.1 A 60 s, 3 phase
Nominal switching frequency
12 kHz
Switching frequency
1...16 kHz adjustable12...16 kHz with derating factor
asynchronous motor control
Voltage/frequency ratio, 2 pointsFlux vector control without sensor, standardVoltage/frequency ratio, 5 pointsVoltage/frequency ratio - Energy Saving, quadratic U/f
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC, +/- 5 %, <10 mA overload and short-circuit protectionInternal supply 24 V DC 21...27 V), <200 mA overload and short-circuit protectionExternal supply 24 V DC 19...30 V)
Analogue input number
2
Analogue input type
AI1-/Al1+ bipolar differential voltage +/- 10 V DC 24 V max 11 bits + signAI2 software-configurable current 0...20 mA 242 Ohm 11 bitsAI2 software-configurable voltage 0...10 V DC 24 V max 30000 Ohm 11 bits
sampling time
2 ms +/- 0.5 ms AI1-/Al1+) - analog input2 ms +/- 0.5 ms Al2) - analog input2 ms +/- 0.5 ms AO1) - analog output2 ms +/- 0.5 ms LI1...LI5) - discrete input2 ms +/- 0.5 ms LI6)if configured as logic input - discrete input
absolute accuracy precision
+/- 0.6 % AI1-/Al1+) for a temperature variation 60 °C+/- 0.6 % AI2) for a temperature variation 60 °C+/- 1 % AO1) for a temperature variation 60 °C
Linearity error
+/- 0.15 % of maximum value AI1-/Al1+)+/- 0.15 % of maximum value AI2)+/- 0.2 % AO1)
Analogue output number
1
Analogue output type
AO1 software-configurable current 0...20 mA 500 Ohm 10 bitsAO1 software-configurable voltage 0...10 V DC 470 Ohm 10 bitsAO1 software-configurable logic output 10 V, 20 mA
<= 100 ms in STO (Safe Torque Off)R1A, R1B, R1C <= 7 ms +/- 0.5 msR2A, R2B <= 7 ms +/- 0.5 ms
Minimum switching current
3 mA 24 V DC configurable relay logic
Maximum switching current
R1, R2 2 A 250 V AC inductive, cos phi = 0.4 7 msR1, R2 2 A 30 V DC inductive, cos phi = 0.4 7 msR1, R2 5 A 250 V AC resistive, cos phi = 1 0 msR1, R2 5 A 30 V DC resistive, cos phi = 1 0 ms
Discrete input number
7
Discrete input type
Programmable LI1...LI5) 24 V DC <= 30 V)level 1 PLC - 3500 OhmSwitch-configurable LI6) 24 V DC <= 30 V)level 1 PLC - 3500 OhmSwitch-configurable PTC probe LI6)0...6 - 1500 OhmSafety input PWR) 24 V DC <= 30 V) - 1500 Ohm
Linear adjustable separately from 0.01 to 9000 sAutomatic adaptation of ramp if braking capacity exceeded, by using resistorS, U or customized
Braking to standstill
By DC injection
Protection type
Against exceeding limit speed driveAgainst input phase loss driveBreak on the control circuit driveInput phase breaks driveLine supply overvoltage driveLine supply undervoltage driveOvercurrent between output phases and earth driveOverheating protection driveOvervoltages on the DC bus drivePower removal driveShort-circuit between motor phases driveThermal protection driveMotor phase break motorPower removal motorThermal protection motor
Insulation resistance
> 1 mOhm 500 V DC for 1 minute to earth
Frequency resolution
Analog input 0.024/50 HzDisplay unit 0.1 Hz
Connector type
1 RJ45 on front face)Modbus1 RJ45 on terminal)ModbusMale SUB-D 9 on RJ45CANopen
Physical interface
2-wire RS 485 Modbus
Transmission frame
RTU Modbus
Transmission rate
4800 bps, 9600 bps, 19200 bps, 38.4 Kbps Modbus on terminal9600 bps, 19200 bps Modbus on front face20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps CANopen
Data format
8 bits, 1 stop, even parity Modbus on front face8 bits, odd even or no configurable parity Modbus on terminal
Number of addresses
1...127 CANopen1...247 Modbus
Method of access
Slave CANopen
marking
CE
Operating position
Vertical +/- 10 degree
Net Weight
12.1 lb(US) (5.5 kg)
Width
6.9 in (175 mm)
Height
11.6 in (295 mm)
Depth
7.4 in (187 mm)
Noise level
55.6 dB 86/188/EEC
Dielectric strength
3535 V DC between earth and power terminals5092 V DC between control and power terminals
Electromagnetic compatibility
Conducted radio-frequency immunity test level 3 IEC 61000-4-6Electrical fast transient/burst immunity test level 4 IEC 61000-4-4Electrostatic discharge immunity test level 3 IEC 61000-4-2Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3Voltage dips and interruptions immunity test IEC 61000-4-11
Standards
EN 61800-3 environments 2 category C3EN/IEC 61800-3EN 55011 class A group 2EN 61800-3 environments 1 category C3EN/IEC 61800-5-1UL Type 1IEC 60721-3-3 class 3C1IEC 60721-3-3 class 3S2
Product Certifications
CSANOM 117DNVC-tickGOSTUL
Pollution degree
2 EN/IEC 61800-5-1
degree of proctection
IP20 on upper part without blanking plate on cover EN/IEC 60529IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1IP21 EN/IEC 60529IP21 EN/IEC 61800-5-1IP41 on upper part EN/IEC 60529IP41 on upper part EN/IEC 61800-5-1IP54 on lower part EN/IEC 60529IP54 on lower part EN/IEC 61800-5-1
Vibration resistance
1 gn 13...200 Hz)EN/IEC 60068-2-61.5 mm peak to peak 3...13 Hz)EN/IEC 60068-2-6
Shock resistance
15 gn 11 ms EN/IEC 60068-2-27
Relative humidity
5...95 % without condensation IEC 60068-2-35...95 % without dripping water IEC 60068-2-3
Ambient air temperature for operation
14...122 °F (-10...50 °C) without derating)122...140 °F (50...60 °C) with derating factor)
Ambient Air Temperature for Storage
-13...158 °F (-25...70 °C)
Operating altitude
<= 3280.84 ft (1000 m) without derating3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m