High-performance analog input module for thermocouple measurements in industrial applications.
Product Model140ATI03000C
Product ID24220
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh common mode rejection (> -120 dB 50/60 Hz) for accurate measurements.
2
FeatureRobust isolation between channels and bus (1780 V AC 60 s, 2500 V DC 60 s) for enhanced safety.
3
FeatureIsolation between channels (300 V) for reliable data transmission.
4
FeatureDesigned for industrial applications requiring precise thermocouple measurements.
5
FeatureCompliant with industrial standards for reliable performance.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Modicon Quantum automation platform
Product or Component Type
Analogue input module
Type of filter
Notch filter - 3 dB at 50/60 HzSingle pole low pass - 3 dB at 20 Hz
Analogue input number
8
Addressing requirement
10 input words
Analogue input type
Thermocouple - 210...760 °C thermocouple JThermocouple - 270...1000 °C thermocouple EThermocouple - 270...1370 °C thermocouple KThermocouple - 270...400 °C thermocouple TThermocouple - 50...1665 °C thermocouple RThermocouple - 50...1665 °C thermocouple S
Analogue input resolution
16 bits
Absolute accuracy error
+/- 2 °C plus + 0.1 % of reading thermocouple E+/- 2 °C plus + 0.1 % of reading thermocouple J+/- 2 °C plus + 0.1 % of reading thermocouple K+/- 2 °C plus + 0.1 % of reading thermocouple T+/- 4 °C plus + 0.1 % of reading thermocouple R+/- 4 °C plus + 0.1 % of reading thermocouple S
Linearity error
1 °C, 0.1 °C, 1 F, 0.1 F - 210...760 °C1 °C, 0.1 °C, 1 F, 0.1 F - 270...1000 °C1 °C, 0.1 °C, 1 F, 0.1 F - 270...1370 °C1 °C, 0.1 °C, 1 F, 0.1 F - 270...400 °C1 °C, 0.1 °C, 1 F, 0.1 F - 50...1665 °C
Accuracy drift according to temperature
0.15 µV/°C + 0.0015 % of reading/°C max low level voltage
Common mode rejection
> - 120 dB 50/60 Hz
Isolation between channels and bus
1780 V AC 60 s2500 V DC 60 s
Isolation between channels
300 V DC220 V AC
Update time
1000 ms
Fault type
Broken wireOvertacking scale
marking
CE
Cold junction compensation
Internal 32...140 °F (0...60 °C)
Local signalling
for bus communication is present (Active) 1 LED (green) for external fault 1 LED (red) for channel is turned on 8 LEDs (green) for channel fault 8 LEDs (red)