Analog input module for thermocouple applications, part of the Modicon Quantum automation platform.
Product Model140ATI03000
Product ID24218
Stock on Request
Last updated: 8/29/2026
Key Features
1
FeatureHigh-performance analog input module designed for thermocouple applications.
2
FeatureCompliant with EU RoHS Directive and China RoHS Regulation for environmental sustainability.
3
FeaturePart of the Green Premium commitment for best-in-class environmental performance.
4
FeatureMercury-free and REACH compliant for safe operation.
5
FeatureIdeal for industrial automation systems requiring precise temperature measurement.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Range of Product
Modicon Quantum automation platform
Product or Component Type
Analogue input module
Type of filter
Notch filter - 3 dB at 50/60 HzSingle pole low pass - 3 dB at 20 Hz
Analogue input number
8
Addressing requirement
10 input words
Analogue input type
Thermocouple - 210...760 °C thermocouple JThermocouple - 270...1000 °C thermocouple EThermocouple - 270...1370 °C thermocouple KThermocouple - 270...400 °C thermocouple TThermocouple - 50...1665 °C thermocouple RThermocouple - 50...1665 °C thermocouple S
Analogue input resolution
16 bits
Absolute accuracy error
+/- 2 °C plus + 0.1 % of reading thermocouple E+/- 2 °C plus + 0.1 % of reading thermocouple J+/- 2 °C plus + 0.1 % of reading thermocouple K+/- 2 °C plus + 0.1 % of reading thermocouple T+/- 4 °C plus + 0.1 % of reading thermocouple R+/- 4 °C plus + 0.1 % of reading thermocouple S
Linearity error
1 °C, 0.1 °C, 1 F, 0.1 F - 210...760 °C1 °C, 0.1 °C, 1 F, 0.1 F - 270...1000 °C1 °C, 0.1 °C, 1 F, 0.1 F - 270...1370 °C1 °C, 0.1 °C, 1 F, 0.1 F - 270...400 °C1 °C, 0.1 °C, 1 F, 0.1 F - 50...1665 °C
Accuracy drift according to temperature
0.15 µV/°C + 0.0015 % of reading/°C max low level voltage
Common mode rejection
> - 120 dB 50/60 Hz
Isolation between channels and bus
1780 V AC 60 s2500 V DC 60 s
Isolation between channels
300 V DC220 V AC
Update time
1000 ms
Fault type
Broken wireOvertacking scale
marking
CE
Cold junction compensation
Internal 32...140 °F (0...60 °C)
Local signalling
for bus communication is present (Active) 1 LED (green) for external fault 1 LED (red) for channel is turned on 8 LEDs (green) for channel fault 8 LEDs (red)