+/- 12 µA max 4...20 mA+/- 6 µA max 0...20 mA+/- 6 µA max 0...25 mA+/- 6 µA max 4...20 mA
Accuracy drift according to temperature
+/- 0.0025 % of full scale/°C<= 0.0050 % of full scale /°C
Common mode rejection
> - 90 dB 60 Hz
Isolation between channels and bus
1780 V AC 60 s
Update time
15 ms 2 wires/4 wires
Fault type
Broken wire 4...20 mA
marking
CE
Local signalling
for bus communication is present (Active) 1 LED (green) for external fault 1 LED (red) for channel is turned on 16 LEDs (green) for channel fault 16 LEDs (red)
Bus current requirement
360 mA
Power dissipation in W
5 W
Module format
Standard
Net Weight
0.7 lb(US) (0.3 kg)
Protective treatment
Conformal coating Humiseal 1A33
Standards
UL 508CSA C22.2 No 142
Product Certifications
FM Class 1 Division 2cUL
Resistance to electrostatic discharge
4 kV contact IEC 801-28 kV on air IEC 801-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80...1000 MHz IEC 801-3
Ambient Air Temperature for Operation
32...140 °F (0...60 °C)
Ambient Air Temperature for Storage
-40...185 °F (-40...85 °C)
Relative Humidity
95 % without condensation
Operating altitude
<= 16404.2 ft (5000 m)
140ACI04000C Analog Input Module - Schneider Electric | INDSLT