Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
762 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
109 kg
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001252R0223
Current Type
AC
Electrical Durability
Ue =< 440 V 3000 cycle Ue = 500 ... 690 V 2000 cycle 10 cycles per hour
Mechanical Durability
12000 cycle 60 cycles per hour
Number of Poles
3P
Power Loss
483 W
Rated Current (I<sub>n</sub>)
5000 A
Rated Impulse Withstand Voltage (U<sub>imp</sub>)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (U<sub>i</sub>)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (I<sub>cs</sub>)
(220 V AC) 100 kA (230 V AC) 100 kA (380 V AC) 100 kA (400 V AC) 100 kA (415 V AC) 100 kA (440 V AC) 100 kA (500 V AC) 100 kA (660 V AC) 100 kA (690 V AC) 100 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (I<sub>cs</sub>)
100 %
Rated Short-time Withstand Current Low Voltage (I<sub>cw</sub>)