Product Net Width
15 mm
Product Net Depth / Length
70 mm
Number of Auxiliary Contacts NC
2
Standards
IEC/EN 60947-5-1, UL 60947-1, UL 60947-5-1, CSA C22.2 No. 60947-1-13, CSA C22.2 No. 60947-5-1-14
Rated Operational Voltage
Auxiliary Circuit 690 V
Rated Frequency (f)
Auxiliary Circuit 50 / 60 Hz
Conventional Free-air Thermal Current (I<sub>th</sub>)
acc. to IEC 60947-5-1, Θ = 40 °C 16 A
Rated Operational Current AC-15 (I<sub>e</sub>)
(500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A
Short-Circuit Protective Devices
Auxiliary Circuit - gG Type Fuses 10 A
Rated Operational Current DC-13 (I<sub>e</sub>)
(24 V) 6 A (48 V) 2.8 A (72 V) 1 A (125 V) 0.55 A (250 V) 0.3 A
Rated Insulation Voltage (U<sub>i</sub>)
acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V
Mechanical Durability
5 million
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
Terminal Type
Screw Terminals
Suitable For
A9 A12 A16 A26 A30 A40 AL9 AL9Z AL12 AL12Z AL16 AL16Z AL26 AL30 AL40 TAL9 TAL12 TAL16 TAL26 TAL30 TAL40 AX06 AX09 AX12 AX18 AX25 AX32 AX40
ETIM 7
EC001044 - Mechanic interlock for switch
ETIM 8
EC001044 - Mechanic interlock for switch
ETIM 9
EC001044 - Mechanic interlock for switch
IDEA Granular Category Code (IGCC)
5219 >> Switch part or accessory
E-Number (Finland)
3709234