High-performance moulded case circuit breaker with front terminals and thermomagnetic release, ideal for reliable power distribution in various electrical applications.
Product ModelXT2V 160 TMD16/300 F F 4P
Material Number2TFC000628R1001
Product ID110748
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliable Power DistributionThe ABB XT2V 160 TMD 16/300 4P FF is engineered to provide reliable power distribution, ensuring consistent performance in demanding electrical environments.
2
2. Front Terminal ConnectionEquipped with front terminals, this circuit breaker offers easy and convenient connections, reducing installation time and improving overall efficiency.
3
3. Thermomagnetic ReleaseThe thermomagnetic release mechanism ensures safe and efficient operation by automatically tripping the circuit in case of an overload or short circuit, protecting your equipment and personnel.
4
4. High DurabilityDesigned to withstand heavy usage, this circuit breaker can handle up to 25,000 operations, making it a durable choice for long-term applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
1SDL000190R0001
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Product Name
Moulded Case Circuit Breaker
5
5. Compliance with International StandardsThe XT2V 160 TMD 16/300 4P FF meets IEC standards, ensuring compliance with international safety and performance regulations, providing peace of mind for your electrical installations.
Product Type
CB
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 1.30 W
Rated Current (In)
16 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
V
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)