ABB XT2N 160 Ekip LSI: 3-pole, 160A, 690V AC circuit breaker with solid-state release for reliable power distribution and system protection.
Product ModelXT2N 160 Ekip LSI In=160A 3p F F
Material Number1SDA067071R1
Product ID86495
Stock on Request
Last updated: 9/6/2026
Key Features
1
1. High Current RatingThe XT2N 160 Ekip LSI supports a rated current of 160A, making it suitable for demanding applications in power distribution systems.
2
2. Solid-State ReleaseEquipped with a solid-state release mechanism, this circuit breaker ensures fast and reliable operation under various electrical conditions.
3
3. Wide Voltage CompatibilityDesigned to operate within a rated voltage range of 220-690V AC, the XT2N 160 Ekip LSI is versatile and can be used in various electrical networks.
4
4. Enhanced Safety FeaturesCompliant with IEC standards and featuring a fixed circuit-breaker design, the XT2N 160 Ekip LSI provides robust protection against short circuits and electrical overloads.
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Circuit Breaker Type to be Associated
Power Distribution
5. Integration with ABB AbilityTM CloudThe SACE Tmax XT series, including the XT2N 160 Ekip LSI, integrates seamlessly with the ABB AbilityTM cloud platform, enabling real-time data analysis and enhanced system monitoring.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 10.80 W
Rated Current (In)
160 A
Rated Frequency (f)
50/60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSI
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)