Short Description: ABB XT2S 160 TMG 32-160 3P FF circuit breaker with thermomagnetic release, designed for high current interruption in industrial settings.
Product ModelXT2S 160 TMG 32-160 3p F F
Material Number1SDA067741R1
Product ID86094
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliable ProtectionThe XT2S 160 TMG provides reliable protection against electrical faults with its thermomagnetic release mechanism, ensuring safe operation in industrial environments.
2
2. High Current InterruptionCapable of interrupting currents up to 160 A, this circuit breaker is ideal for applications requiring high current handling and quick fault detection.
3
3. Industrial GradeDesigned for the demands of industrial settings, the XT2S 160 TMG is built to withstand harsh conditions and ensure continuous operation.
4
4. Efficient OperationWith a fast response time and high interrupting capacity, this circuit breaker minimizes downtime and ensures efficient operation in critical applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Generator Protection
5
5. Compliance and StandardsMeets IEC standards for electrical safety and performance, ensuring compliance with global regulations and industry standards.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.57 W
Rated Current (In)
32 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
160 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMG
Release Type
TM
Setting Range
22.4...32 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)