Short Description: High-performance moulded case circuit breaker with thermomagnetic release, suitable for AC/DC applications, and designed for power distribution systems.
Product ModelXT2N 160 TMD 16-300 3p F F
Material Number1SDA067010R1
Product ID84327
Stock on Request
Last updated: 9/6/2026
Key Features
1
1. Reliable Protection DescriptionThe ABB XT2N 160 TMD 16-300 3P FF offers reliable protection for your power distribution systems with its thermomagnetic release, ensuring that your equipment is safeguarded against short circuits and overloads.
2
2. Versatile Application DescriptionThis circuit breaker is designed for both AC and DC applications, making it versatile and adaptable to a wide range of electrical systems, including power distribution, cables, generators, and motors.
3
3. High Performance DescriptionWith a rated current of 16 A and a rated voltage of 690 V AC/500 V DC, the XT2N 160 TMD 16-300 3P FF delivers high performance in demanding electrical environments, ensuring efficient operation and minimal downtime.
4
4. Compliance with Standards DescriptionThe product meets IEC standards, ensuring compliance with international safety and performance requirements. This guarantees that the circuit breaker operates safely and effectively in various electrical systems.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
5
5. Durable Design DescriptionBuilt to last, the XT2N 160 TMD 16-300 3P FF has a durable design with a net height of 130 mm and a net depth of 82.5 mm, making it a reliable choice for long-term use in various industrial settings. Its mechanical durability supports up to 25,000 cycles, ensuring consistent performance over time.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.33 W
Rated Current (In)
16 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
300 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
11.2...16 A
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)