ABB XT2S 160 TMD 5-50 4p F F: A high-performance, thermomagnetic release molded case circuit breaker designed for reliable power distribution in industrial applications.
Product ModelXT2S 160 TMD 5-50 4p F F
Material Number1SDA067566R1
Product ID84200
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. High Breaking CapacityThe XT2S 160 TMD 5-50 4p F F boasts a breaking capacity of 50 kA, ensuring reliable operation under short-circuit conditions.
2
2. Thermomagnetic ReleaseEquipped with a thermomagnetic release (TMD) mechanism, this circuit breaker provides efficient and reliable tripping in case of overcurrent conditions.
3
3. Four-Pole ConfigurationDesigned with a four-pole configuration, it offers flexibility and compatibility with various electrical systems, enhancing overall system reliability.
4
4. Electrical DurabilityBuilt to withstand 120 cycles per hour and 8000 cycles in total, this circuit breaker ensures long-lasting performance and durability in demanding industrial environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Power Distribution
5
5. Compliance with IEC StandardsMeets IEC standards, ensuring compliance with international safety and performance regulations, making it a trusted choice for global industrial applications.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4. W
Rated Current (In)
5 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
50 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
3.5...5 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067566R1
ABB XT2S 160 TMD 5-50 4p F F - High-Performance Circuit Breaker | INDPRT