High-performance, fixed four-pole circuit breaker with thermomagnetic release for 690V applications, ensuring reliable short-circuit breaking capacity.
Product ModelXT2S 160 TMD 1,6-16 4p F F
Material Number1SDA067561R1
Product ID84194
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliable Short-Circuit Breaking CapacityThe XT2S 160 TMD 1,6-16 4p F F circuit breaker provides a robust short-circuit breaking capacity of up to 85 kA at 220V AC, ensuring safe and efficient operation under demanding conditions.
2
2. Thermomagnetic ReleaseEquipped with a thermomagnetic release mechanism, this circuit breaker offers reliable and fast operation in case of short circuits, ensuring minimal downtime and maximum safety.
3
3. Front Terminal ConnectionThe front terminal connection type makes installation and maintenance easier, reducing the time and effort required for setup and repair.
4
4. High Electrical DurabilityDesigned to withstand 240 cycles per hour and 25,000 operational cycles, this circuit breaker is built to last, providing long-term reliability in various electrical applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Power Distribution
5
5. Compliance with IEC StandardsThe XT2S 160 TMD 1,6-16 4p F F circuit breaker meets all necessary IEC standards, ensuring compliance with international safety and performance regulations.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2 W
Rated Current (In)
1.6 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
16 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
1.12...1.6 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067561R1
ABB XT2S 160 TMD 1,6-16 4p F F Circuit Breaker - High Performance | INDPRT