High-performance moulded case circuit breaker with thermomagnetic release and front terminal connection, suitable for 500A main circuit applications.
Product ModelT5N 630 TMA 500-5000 3p F F
Material Number1SDA054456R1
Product ID76061
Stock on Request
Last updated: 9/6/2026
Key Features
1
1. High Electrical DurabilityThe T5N 630 TMA 500-5000 3p F F is designed to withstand 5000 cycles at 60 cycles per hour, ensuring long-lasting performance in demanding electrical environments.
2
2. Thermomagnetic ReleaseEquipped with a thermomagnetic release (TMA) that provides reliable short-circuit protection, ensuring the safety of your electrical system.
3
3. Front Terminal ConnectionFeatures front terminal connections for easy installation and maintenance, reducing downtime and increasing operational efficiency.
4
4. IEC ComplianceMeets IEC standards for short-circuit breaking capacity, ensuring compliance with international safety and performance regulations.
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK10103A1056 9AKK108467A6707
Product Net Width
140 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
4.579 kg
Product Main Type
SACE Tmax T
5. Versatile Voltage CompatibilityCompatible with a wide range of voltages, including 220 V AC, 230 V AC, 380 V AC, and 690 V AC, making it suitable for various industrial applications.
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T5
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
5000 cycle 60 cycles per hour
Mechanical Durability
20000 cycle 120 cycles per hour
Number of Poles
3
Power Loss
at Rated Operating Conditions per Pole 28.8 W
Rated Current (In)
500 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA
(220 V AC) 70 kA (230 V AC) 70 kA (380 V AC) 36 kA (400 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 30 kA (500 V AC) 25 kA (690 V AC) 20 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 25 kA (750 V DC) 3 Poles in Series 16 kA
Rated Uninterrupted Current (Iu)
630 A
Release
TMA
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC
Sub-type
T5
Terminal Connection Type
Fixed Circuit-Breakers Front
Test Voltage Max (Utest)
3500 V
Test Voltage at Industrial Frequency for 1 Minute
3500 V
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39121100
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA054456R1