Short Product Description High-performance, three-pole moulded case circuit breaker with solid-state release and front terminals for reliable industrial automation.
Product ModelT4V 250 PR222DS/P-LSI In=250 3p F F
Material Number1SDA054101R1
Product ID75019
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. High Performance and ReliabilityThe ABB T4V 250 PR222DS/P-LSI In=250 3p FF is engineered to provide high-performance and reliability in industrial automation settings. Its solid-state release ensures consistent and efficient operation, even under demanding conditions.
2
2. Advanced TechnologyEquipped with the latest technology, this circuit breaker features advanced arcing chambers that reduce arc extinction time, enhancing overall performance and safety.
3
3. Versatile ConnectivityThe product offers versatile connectivity options with front terminals, making it easy to integrate into various industrial setups. This flexibility ensures seamless integration with existing infrastructure.
4
4. Enhanced Safety FeaturesDesigned with safety in mind, the T4V 250 PR222DS/P-LSI In=250 3p FF includes double insulation for greater safety, reducing the risk of electrical shock and ensuring a secure working environment.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK10103A1057
Product Net Width
105 mm
Product Net Height
205 mm
Product Net Depth / Length
103.5 mm
Product Net Weight
3.5 kg
Product Main Type
SACE Tmax T
5
5. Compliance with International StandardsThe circuit breaker complies with international standards such as IEC 60947, ensuring it meets the highest safety and performance requirements. This compliance provides peace of mind for users in diverse industrial settings.
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable For
T4
Suitable for Product Class
Moulded Case Circuit Breakers
Version
F
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
20000 cycle 240 cycles per hour
Number of Poles
3
Power Loss
at Rated Operating Conditions per Pole 10.7 W
Rated Current (In)
250 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (380 V AC) 200 kA (400 V AC) 200 kA (415 V AC) 200 kA (440 V AC) 180 kA (500 V AC) 150 kA (690 V) 150 kA